Fresh Air Intake Kit: Oaci-160K3 - York HIC4008B21S Engineering Manual

Inverter-driven multi-split system heat pump air conditioner
Hide thumbs Also See for HIC4008B21S:
Table of Contents

Advertisement

3.5 Fresh Air Intake Kit: OACI-160K3

Dimensional Data
33-7/16 [850]
27-9/16 [700]
(Decorative Panel Mounting Position)
Galvanized Steel Plate
AIR FLOW
Mounting Hook
(4 Places)
Fresh Air
Dedicated Outside
Air System
30-1/2 [775]
Installation State
Side View
P
33-1/16 [840]
Indoor Unit
Insulation
Fresh Air
Intake Kit
Dimension
Indoor Unit
008 to 018 MBH
11-7/16 [291]
024 to 048 MBH
13-7/16 [341]
Specifications
Item
Applicable Indoor Unit Model
((H,Y,C)IC4**B21S)
Material
Color of Frame
Weight
Applicable T-Tube Connecting Kit (Option)
NOTES:
1. This kit cannot supply fresh air without connecting a duct from a dedicated outside air system or duct fan.
2. When using this kit with the dedicated outside air system, the maximum fresh air intake volume should be
within 20% of the rated airflow volume of the indoor unit. In addition, when using this kit without the dedicated
outside air system, care should be taken to not cause condensation inside this kit, the duct, and indoor unit.
3. The total height of the unit is increased by approximately 2-3/16 inches (55mm) when the fresh air inlet kit is
installed. Pay attention to the amount of space needed for installation.
4. When fresh air is taken from one side, cover the gap with insulation for the other side to prevent air leakage
and condensation.
5. Air flowing through the duct does not pass through the air filter of the indoor unit. Therefore, install an air filter
(field-supplied) at the supply side of the fresh air.
6. Insulate the duct and the duct connection (including the plate band and the T-tube connection).
The materials for the duct and the insulation should be nonflammable.
7. The curve "Pass Resistance of Fresh Air Intake Portion" shows the value when the kit is used by itself. If the
kit is installed along with the T-tube connecting kit, refer to the "T-Tube Connecting Kit" for details.
8. Refer to the "Installation Manual for Fresh Air Intake Kit" for installation details.
TC-17005-rev.1
Polystyrene
AIR FLOW
Ø2-15/16 [75]
Ceiling
Decorative Panel
(Option)
Air Inlet Grille
(Attached with Decorative Panel)
a
b
9-5/16 [236]
11-1/4 [286]
Model
MBH
lbs (kg)
2-3/16 [55]
(Height of Filter Box)
13/16 [20]
3/8 [10]
(Before Compression)
1-15/16 [50]
Insulation
(EPDM)
Insulation
(Polyethylene)
Connecting Box
(Accessory)
3-1/8 [80]
Flange Ø2-15/16 [75]
(Accessory)
6-7/8
[174]
View from P
29-15/16 [760]
Ø2-15/16 [75]
T-Tube Connection
Kit Ø2-15/16 [75]
(Option)
27-3/4 [705]
33-1/16 [840]
33-7/8 to 35-13/16 [860 to 910]
(Dimension for Opening)
Polyethylene, Galvanized Steel Plate, EPDM-FO, Polystyrene
OPTIONAL PARTS
Unit: inch [mm]
Pass Resistance of
Fresh Air Intake Portion
0.25
0.20
036 MBH Model
Limit of Fresh Air
Intake Amount
0.15
0.10
0.05
0
0
25
50
05
0
100
150
Air Volume (cfm)
*1) Installation of the connecting box at one side.
*2) Installation of the connecting box at both side.
Electrical Control Box
If this dimension is
1-9/16 inches [40mm] or less,
the ceiling slab will interfere with
the connecting box.
(3-3/8 [85])
Ø2-15/16 [75]
Flexible Duct
Ø5-7/8 [150]
(Field-Supplied)
Fresh Air
Dedicated Outside
Air System
OACI-160K3
008 to 048
Bluish Gray
5.1 (2.3)
TKCI-160K
75
100
125
150
(*1)
200
250
300
(*2)
3-5