Operation Space; Sensible Heat Factor (Shf) - York HIC4008B21S Engineering Manual

Inverter-driven multi-split system heat pump air conditioner
Hide thumbs Also See for HIC4008B21S:
Table of Contents

Advertisement

4-WAY CASSETTE

2.7 Operation Space

Models: (H,Y,C)IC4008B21S, (H,Y,C)IC4012B21S, (H,Y,C)IC4015B21S, (H,Y,C)IC4018B21S,
(H,Y,C)IC4024B21S, (H,Y,C)IC4030B21S, (H,Y,C)IC4036B21S and (H,Y,C)IC4048B21S
Min.
19-11/16
(500)
Piping Connection
Min. 59-1/16 (1500)
Piping
Connection
Side
Min. 59-1/16 (1500)

2.8 Sensible Heat Factor (SHF)

Model
(H,Y,C)IC4008B21S
(H,Y,C)IC4012B21S
(H,Y,C)IC4015B21S
(H,Y,C)IC4018B21S
(H,Y,C)IC4024B21S
(H,Y,C)IC4030B21S
(H,Y,C)IC4036B21S
(H,Y,C)IC4048B21S
* SHF is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature: 95
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft. (0m)
2-10
Min.
Min.
19-11/16
19-11/16
(500)
(500)
Piping Connection
Min. 59-1/16 (1500)
Min. 59-1/16 (1500)
Distance from Wall Side
SHF *
0.77
0.77
0.78
0.89
0.81
0.83
0.83
0.83
o
80
F DB (26.7
o
67
F WB (19.4
o
F DB (35.0
Min.
Min.
118-1/8
19-11/16
(3000)
(500)
Piping Connection
Service Space
o
C DB)
o
C WB)
o
C DB)
Unit: inch (mm)
Min.
94-1/2
(2400)
Min. 3/8 (10)
Clearance
008 to 018 Model: 9-3/4 (248)
024 to 048 Model: 11-3/4 (298)
(Unit Height in False Ceiling)
Condensate Piping
Down Slope
Gradient: 1/25 to 1/100
TC-17005-rev.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents