Shunt Release Connection Data - Siemens SENTRON 3VL System Manual

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Technical data

12.15 Shunt release connection data

12.15
Shunt release connection data
Maximum connection lengths of the shunt releases depending on Vn
The table below lists the maximum lengths for the connecting cables of the shunt releases of
family 1 (VL160X to VL400) and/or 2 (VL630 to VL1600). The values in the table refer to
100% V
account.
Table 12- 48 Shunt release family 1
MLFB
Rated voltage in V
From-to
3VL9400-1SC00
24
3VL9400-1SJ00
48
3VL9400-1SK00
110
3VL9400-1SQ00
220
3VL9400-1SM00
48
3VL9400-1SR00
110
3VL9400-1ST00
208
3VL9400-1SV00
380
Table 12- 49 Shunt release family 2
MLFB
Rated voltage in V
From-to
3VL9800-1SC00
24
3VL9800-1SJ00
48
3VL9800-1SK00
110
3VL9800-1SQ00
220
3VL9800-1SM00
48
3VL9800-1SR00
110
3VL9800-1ST00
208
3VL9800-1SV00
380
184
in the case of the shunt releases. A cable loss of 30 % V
n
24
60
127
250
60
127
277
600
24
60
127
250
60
127
277
600
A = 0.5 mm
l
in m
max
DC
10.71
DC
52.97
DC
216.69
DC
999.20
AC
52.97
AC
216.69
AC
626.00
AC
6982.33
A = 0.5 mm
l
in m
max
DC
10.11
DC
38.52
DC
240.77
DC
770.46
AC
38.52
AC
240.77
AC
770.46
AC
4755.21
has been taken into
n
A = 1 mm
A = 1.5 mm
2
2
l
in m
l
max
21.43
32.14
105.94
158.91
433.39
650.08
1998.39
2997.59
105.94
158.91
433.39
650.08
1252.00
1878.01
13964.66
20946.99
A = 1 mm
A = 1.5 mm
2
2
l
in m
l
max
20.22
30.34
77.05
115.57
481.54
722.31
1540.93
2311.39
77.05
115.57
481.54
722.31
1540.93
2311.39
9510.42
14265.62
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
2
in m
max
2
in m
max