Undervoltage Release Connection Data - Siemens SENTRON 3VL System Manual

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

Technical data

12.13 Undervoltage release connection data

12.13
Undervoltage release connection data
Maximum connection lengths of the undervoltage releases depending on V
The table below lists the maximum lengths for the connecting cables of the undervoltage
release family 1 (VL160X to VL400) and/or 2 (VL630 to VL1600). The values in the table
refer to 100% V
taken into account.
Table 12- 44 Undervoltage release family 1
MLFB
Rated voltage in V
From-to
3VL9400-1UN00
12
3VL9400-1UP00
24
3VL9400-1UU00
48
3VL9400-1UV00
60
3VL9400-1UR00
110
3VL9400-1US00
220
3VL9400-1UD00
24
3VL9400-1UG00
110
3VL9400-1UM00
208
3VL9400-1UH00
220
3VL9400-1UQ00
277
3VL9400-1UJ00
380
3VL9400-1UK00
440
3VL9400-1UL00
525
180
in the case of the undervoltage releases. A cable loss of 15% V
n
12
DC
24
DC
48
DC
60
DC
127
DC
250
DC
24
AC
127
AC
208
AC
250
AC
277
AC
415
AC
480
AC
550
AC
n
A = 0.5 mm
A = 1 mm
2
l
in m
l
in m
max
max
0.93
1.85
3.66
7.32
11.79
23.57
21.98
43.97
99.59
199.17
362.13
724.26
1.78
3.57
41.00
82.01
97.18
194.35
153.40
306.80
176.75
353.51
438.14
876.28
559.36
1118.72
607.60
1215.21
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
has been
n
A = 1.5 mm
2
2
I
in m
max
2.78
10.98
35.36
65.95
298.76
1086.40
5.35
123.01
291.53
460.20
530.26
1314.42
1678.08
1822.81