Capacitor banks

Selection of the circuit breaker for protecting and switching capacitors
This table takes account of only a few typical applications and combinations. The appropriate
selection must be made for all other applications.
Table 12- 37 Selection examples for capacitor protection circuits
Rated voltage
230 V
400 V
415 V
525 V
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
Q
capacitor bank
c
[50 Hz]
power [kvar]
15
30
25
50
100
20
40
25
50
Capacitor rated
Upstream SENTRON VL circuit breaker
current
Type
x 1.5 = I
of the
R
SENTRON VL [A]
56
VL160
113
VL160
54
VL160
108
VL160
216
VL250
42
VL160
84
VL160
42
VL160
84
VL160
Technical data
12.9 Capacitor banks
I
[A]
I
[A]
R
i
50-63
600
100-125
1000
50-63
600
100-125
1000
200-250
2000
40-50
600
80-100
1000
40-50
600
80-100
1000