Power Loss - Siemens SENTRON 3VL System Manual

Switching/protection devices, molded-case circuit breakers
Hide thumbs Also See for SENTRON 3VL:
Table of Contents

Advertisement

12.6

Power loss

Power loss for fixed-mounted circuit breakers
Thermomagnetic overcurrent trip units (TM)
The table below shows the power loss and the current path resistance for thermomagnetic
overcurrent trip units (TM). The power loss applies for I
specified power loss is the sum of all current paths. The current path resistance is only a
guide value and can fluctuate.
Table 12- 29 Power loss for thermomagnetic overcurrent trip units (TM)
VL160X
VL160
VL250
VL400
VL630
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
Type
Rated current [A]
n
Power loss [W]
16
11
20
17
25
32
11
40
16
50
15
63
18
80
24
100
22
125
31
160
41
50
16
63
21
80
27
100
27
125
36
160
55
200
60
250
71
200
60
250
84
315
120
400
175
315
85
400
120
500
170
630
230
Technical data
12.6 Power loss
with 3-phase balanced load. The
Path resistance [mΩ]
7
3,7
3,6
3,3
2,0
1,5
1,3
0.73
0,66
0,53
2,1
1,8
1,4
0,90
0,77
0,63
0,47
0,38
0,50
0,45
0,40
0,36
0,29
0,25
0,23
0,19
14
14
167