Download Print this page
Belimo LRB24-3 Quick Start Manual

Belimo LRB24-3 Quick Start Manual

On/off, floating point, non-spring return, 24 v
Hide thumbs Also See for LRB24-3:

Advertisement

Quick Links

LRB24-3
On/Off, Floating Point, Non-Spring Return, 24 V
Technical Data
Power Supply
24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
Power Consumption Running 1.5 W
Power Consumption Holding 0.2 W
Transformer Sizing
2.5 VA (class 2 power source)
Electrical Connection
3ft [1m], 18 GA plenum cable with 1/2" conduit
connector
Overload Protection
electronic thoughout 0° to 90° rotation
Input Impedance
600 Ω
Angle of Rotation
90°
Direction of Rotation (Motor) reversible with built-in switch
Position Indication
integrated into handle
Manual Override
external push button
Running Time (Motor)
90 sec
Ambient Temperature Range
-22°F to 122°F [-30°C to 50°C]
Storage Temperature Range
-40°F to 176°F [-40°C to 80°C]
Housing
NEMA 2, IP54, UL Enclosure Type 2
Agency Listings†
cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC
Noise Level (Motor)
<35 dB (A)
Servicing
maintenance free
Quality Standard
ISO 9001
†Rated Impulse Voltage 800V, Type action 1.B , Control Pollution Degree 3.
800-543-9038 USA
2253
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN

Advertisement

loading
Need help?

Need help?

Do you have a question about the LRB24-3 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Belimo LRB24-3

  • Page 1 LRB24-3 On/Off, Floating Point, Non-Spring Return, 24 V Technical Data 2253 Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power Consumption Running 1.5 W Power Consumption Holding 0.2 W Transformer Sizing 2.5 VA (class 2 power source) Electrical Connection 3ft [1m], 18 GA plenum cable with 1/2”...
  • Page 2 LRB24-3 On/Off, Floating Point, Non-Spring Return, 24 V Wiring Diagrams 24 VAC Transformer INSTALLATION NOTES Provide overload protection and disconnect as required. Line Blk (1) Common Actuators may be connected in parallel. Power consumption and input Volts Red (2) + Hot impedance must be observed.