Modulating damper actuator for adjusting dampers in technical building installations (4 pages)
Summary of Contents for Belimo CMU Series
Page 1
Damper Actuators Technical Databook Ver. 2 Version 4 Belimo Asia Pacific...
Page 2
Open/Close (only for CMU230..) -RES Modulating DC 2(0)...10V Control Auxiliary Switch Form fit Terminal Connection Mechanical Fail-Safe Damper Actuator Open/Close Blank Modulating DC 2(0)...10V Control 3-point Auxiliary Switch -S, -S2 For customising types of Damper Actuators please contact your nearest Belimo sales representative.
TF24-3 TF24-SR TF230(-S) TF230-SR Mechanical Fail-Safe Damper Actuator, 4Nm Note: LF24(-S) Using Belimo Damper Actuators: LF24-3 The actuators listed in this catalogue are intended for the • LF24-SR operation of air dampers in HVAC systems. LF230(-S) The Damper Actuator is not allowed to be used outside the •...
Page 12
LMU230(-S/-F) • For operation of air control dampers in HVAC system • Torque: • Nominal voltage: AC 100...240V • Control: Open/Close or 3-point Technical data Nominal voltage Electrical data AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 1.5W @ running / 0.5W @ holding Wire/transformer sizing 3.5VA Auxiliary switch LMU230-S...
Page 13
LMU230SR • For operation of air control dampers in HVAC system • Torque: • Nominal voltage: AC 100...240V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 2.0W @ running / 1W @ holding...
Page 14
NMU24(-S/-F/-T) • For operation of air control dampers in HVAC system • Torque: 10Nm • Nominal voltage: AC/DC 24V • Control: Open/Close or 3-point Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC/DC 19.2...28.8V Power consumption 1.5W @ running / 0.2W @ holding Wire/transformer sizing...
Page 15
NMU24-SR • For operation of air control dampers in HVAC system • Torque: 10Nm • Nominal voltage: AC/DC 24V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC/DC 19.2...28.8V Power consumption...
Page 16
NMU230(-S/-F) • For operation of air control dampers in HVAC system • Torque: 10Nm • Nominal voltage: AC 100...240V • Control: Open/Close or 3-point Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 2.5W @ running / 0.6W @ holding Wire/transformer sizing 5.5VA...
Page 17
NMU230SR For operation of air control dampers in HVAC system Torque: 10Nm Nominal voltage: AC 100... 240V Control signal: DC 2(0)...10V Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 3.5W @ running / 1W @ holding Wire/transformer sizing 6.5VA...
Page 18
SMU24(-S/-F/-T) • For operation of air control dampers in HVAC system • Torque: 20Nm • Nominal voltage: AC/DC 24V • Control: Open/Close or 3-point Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC/DC 19.2...28.8V Power consumption 2W @ running / 0.2W @ holding Wire/transformer sizing...
Page 19
SMU24-SR • For operation of air control dampers in HVAC system • Torque: 20Nm • Nominal voltage: AC/DC 24V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC/DC 19.2...28.8V Power consumption...
Page 20
SMU230(-S/-F) • For operation of air control dampers in HVAC system • Torque: 20Nm • Nominal voltage: AC 100...240V • Control: Open/Close or 3-point Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 2.5W @ running / 0.6W @ holding Wire/transformer sizing Auxiliary switch SMU230-S...
Page 21
SMU230-SR • For operation of air control dampers in HVAC system • Torque: 20Nm • Nominal voltage: AC 100...240V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 3.5W @ running / 1W @ holding...
Page 22
GMU24 • For operation of air control dampers in HVAC system • Torque: 40Nm • Nominal voltage: AC/DC 24V • Control: Open/Close Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC/DC 19.2...28.8V 4W @ running / 2W @ holding Power consumption Wire/transformer sizing Connection cable...
Page 23
GMU24-SR • For operation of air control dampers in HVAC system • Torque: 40Nm • Nominal voltage: AC/DC 24V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC/DC 19.2...28.8V Power consumption...
Page 24
GMU230 • For operation of air control dampers in HVAC system • Torque: 40Nm • Nominal voltage: AC 100...240V • Control: Open/Close Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Nominal voltage range AC 85...265V Power consumption 5W @ running / 2W @ holding Wire/transformer sizing Connection cable Cable 1m, 3x0.75mm...
Page 25
LMQU24 • For operation of air control dampers in HVAC system • Torque: • Nominal voltage: AC/DC 24V • Control: Open/Close (not made for 3-point applications) Technical data Nominal voltage Electrical data AC 24V 50/60Hz, DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption 13W @ running / 1.5W @ holding...
Page 26
LMQU24-SR • For operation of air control dampers in HVAC system • Torque: • Nominal voltage: AC/DC 24V • Control modulating: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption 13W @ running / 1.5W @ holding...
Page 27
NMQU24 • For operation of air control dampers in HVAC system • Torque: • Nominal voltage: AC/DC 24V • Control: Open/Close (not made for 3-point applications) Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption 13W @ running /1.5W @ holding...
Page 28
NMQU24-SR • For operation of air control dampers in HVAC system • Torque: • Nominal voltage: AC/DC 24V • Control modulating: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption 13W @ running / 1.5W @ holding...
Page 29
SMQU24 • For operation of air control dampers in HVAC system • Torque: 16Nm • Nominal voltage: AC/DC 24V • Control: Open/Close (not made for 3-point applications) Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption 15W @ running /1.5W holding...
Page 30
SMQU24-SR • For operation of air control dampers in HVAC system • Torque: 16Nm • Nominal voltage: AC/DC 24V • Control modulating: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Nominal voltage range AC 19.2...28.8V / DC 21.6...28.8V Power consumption...
Page 31
Mechanical Fail-Safe Damper Actuator TF24(-S) • For operation of air control dampers that perform safety function • Torque: • Nominal voltage: AC/DC 24V • Control: Open/Close • Integrated auxiliary switch (TF24-S) Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Power supply range AC 19.2...28.8V, DC 21.6...28.8V Power consumption...
Page 32
Mechanical Fail-Safe Damper Actuator TF24-3 • For operation of air control dampers that perform safety function • Torque: • Nominal voltage: AC 24V • Control: 3-point Technical data Electrical data Nominal voltage AC 24V 50/60Hz Nominal supply range AC 19.2...28.8V Power consumption 2.5W @ running / 1W @ holding Wire/transformer sizing...
Page 33
Mechanical Fail-Safe Damper Actuator TF24-SR • For operation of air control dampers that perform safety function • Torque: • Nominal voltage: AC/DC 24V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Power supply range AC 19.2...28.8V, DC 21.6...28.8V Power consumption...
Page 34
Mechanical Fail-Safe Damper Actuator TF230(-S) • For operation of air control dampers that perform safety function • Torque: • Nominal voltage: AC 100...240V • Control: Open/Close • Integrated auxiliary switch (TF230-S) Technical data Nominal voltage Electrical data AC 100...240V 50/60Hz Nominal supply range AC 85...265V Power consumption...
Page 35
Mechanical Fail-Safe Damper Actuator TF230-SR • For operation of air control dampers that perform safety function • Torque: • Nominal voltage: AC 100...240V • Control signal: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Electrical data Nominal voltage AC 100...240V 50/60Hz Power supply range AC 85...265V Power consumption...
Page 36
Mechanical Fail-Safe Damper Actuator LF24(-S) • For the operation of air dampers that perform safety function • Torque: • Nominal voltage: AC/DC 24V • Control: Open/Close • Integrated auxiliary switch (LF24-S) Technical data Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V Power supply range AC 19.2...28.8V, DC 21.6...28.8V Power consumption...
Page 39
Mechanical Fail-Safe Damper Actuator LF230(-S) • For the operation of air dampers that perform safety function • Torque: • Nominal voltage: AC 230V • Control: Open/Close • Integrated auxiliary switch (LF230-S) Technical data Electrical data Nominal voltage AC 230V 50/60Hz Nominal supply range AC 198...264V Power consumption...
Page 40
Mechanical Fail-Safe Damper Actuator NFU Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations • Torque: 10Nm • Nominal voltage: AC 24...240V/DC 24...125V • Control: Open/Close Technical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V Electrical data Nominal voltage range AC 19.2...264V, DC 20.4...126.5V...
Page 41
Mechanical Fail-Safe Damper Actuator NFU-S2 Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations • Torque: 10Nm • Nominal voltage: AC 24...240V/DC 24...125V • Control: Open/Close • 2x SPDT auxiliary switches built-in Technical data Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V...
Page 42
Mechanical Fail-Safe Damper Actuator NFU24-SR Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations • Torque: 10Nm • Nominal voltage: AC/DC 24V • Control: modulating DC 2(0)...10V position feedback DC 2...10V Technical data Nominal voltage AC 24V 50/60Hz, DC 24V Electrical data...
Page 43
Mechanical Fail-Safe Damper Actuator SFU Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations • Torque: 20Nm • Nominal voltage: AC 24...240V DC 24...125V • Control: Open/Close Technical data Electrical data Nominal voltage AC 24...240V 50/60Hz, DC 24...125V AC 19.2...264V, DC 20.4...126.5V Nominal voltage range...
Page 44
Mechanical Fail-Safe Damper Actuator SFU-S2 Damper actuator for operating air control dampers in ventilation and air-conditioning systems for building services installations • Torque: 20Nm • Nominal voltage: AC 24...240V DC 24...125V • Control: Open/Close • 2x SPDT auxiliary switches built-in Technical data Electrical data Nominal voltage...
Page 45
Mechanical Fail-Safe Damper Actuator SFU24-SR Modulating Mechanical Fail-Safe Actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings • Torque: 20Nm • Nominal voltage: AC/DC 24V • Control Modulating: DC 2(0)...10V • Position feedback: DC 2...10V Technical data Nominal voltage Electrical data...
Page 56
Wiring diagrams — General Damper Actuator Wiring diagrams : CMU.. series actuators Notes: • Parallel connection of several actuators is possible. • Power consumption must be observed. Open/Close control 3-point control Connection via safety isolated transformer AC/DC 24V AC/DC 24V CMU24(-T) CMU24(-T) CMU24-F8(-F10)
Page 57
Wiring diagrams—General Damper Actuator Wiring diagrams: Open/Close actuators—Parallel connection possible, please note the performance data 1-wire control 2-wire control Connection via safety Connection via safety isolated transformer isolated transformer AC/DC 24V AC/DC 24V Direction of rotation Direction of rotation (while direction of rotation reverses) (while direction of rotation reverses)
Page 58
Wiring diagrams—Mechanical Fail-Safe Damper Actuator Wiring diagrams: Open/Close actuators Notes: • Parallel connection of several actuators is possible. • Power consumption must be observed. AC 100...240V (for TF230..) N L1 N L1 AC 230V (for LF230..) Connect via safety AC/DC 24V AC/DC 24V Connect via safety isolating transformer...
Page 59
Wiring diagrams—Mechanical Fail-Safe Damper Actuator Wiring diagrams: 3-point actuators Notes: • Connection via safety isolating transformer. • Parallel connection of several actuators is possible. • Power consumption must be observed. Mounting side Connect via safety AC 24V isolating transformer Reversing switch (Y 1 ) (Y 2 ) stop...
Page 60
Wiring diagrams—Mechanical Fail-Safe Damper Actuator Wiring diagram: Modulating actuators Notes: • Connection via safety isolating transformer. • Parallel connection of several actuators is possible. • Power consumption must be observed. Mounting side AC/DC 24V Connect via safety isolating transformer – Y DC 2(0)...10V U DC 2...10V Reversing switch...
Auxiliary switch adjustment Auxiliary switch adjustment for General Damper Actuators 1. Press the pushbutton, manually operate the universal clamp to desired switch position. 2. Turn switch pointer to the middle line. 3. When actuator moves clockwise (counter clockwise) to switch position, switch indicator passes the middle line counter clockwise (clockwise), the contact between S1 and S3 is disconnected (connected) and the contact between S1 and S2 is connected...
Page 67
Market Asia Pacific ASIA PACIFIC HEADQUARTERS Japan Office: Belimo Actuators Ltd. Belimo Actuators (Shanghai) Trading Ltd. 7th Floor, Honjo-Azumabashi DJ Building 479 Chun Dong Road, Building C-2 4-19-3, Honjo, Sumida-ku Xin Zhuang Industry Park Tokyo 130-0004, Japan Shanghai 201108, P.R. China...
Page 68
Innovation, Quality and Consultancy: A partnership for motorising HVAC Actuators BELIMO Automation AG BELIMO Actuators (Shanghai) Trading Ltd. BELIMO Aircontrol (USA), Inc. Brunnenbachstrasse 1 479 Chun Dong Road, Building C-2 43 Old Ridgebury Road 8340 Hinwil, Switzerland Xin Zhuang Industry Park...