Table Of Outdoor Unit Failure Mode Recall Function - Mitsubishi Electric MXZ-2C20NA2-U1 Service Manual

Outdoor unit
Hide thumbs Also See for MXZ-2C20NA2-U1:
Table of Contents

Advertisement

The left lamp of
OPERATION IN-
Abnormal point
DICATOR lamp
(Failure mode/protection)
(Indoor unit)
OFF
None (Normal)
2-time blink
Outdoor power system
3-time blink
Discharge temperature thermistor
Defrost thermistor
Ambient temperature thermistor
Fin temperature thermistor
P.C. board temperature thermistor
Outdoor heat exchanger tem-
perature thermistor
4-time blink
Overcurrent
5-time blink
Discharge temperature
6-time blink
High pressure
7-time blink
Fin temperature
P.C. board temperature
8-time blink
Outdoor fan motor
9-time blink
Outdoor control system
10-time blink
Low discharge temperature
protection
11-time blink
Communication error
between P.C. boards
Current sensor
Zero cross detecting circuit
Converter
Bus-bar voltage
15-time blink
LEV and drain pump
OBH702G
NOTE: Blinking patterns of this mode differ from the ones of
LED indication
(Outdoor P.C.
Condition
board)
LED 1
LED 2
Lit
Lit
Lit
Lit
Overcurrent protection cut-out operates
3 consecutive times within 1 minute after
the compressor gets started, or converter
protection cut-out or bus-bar voltage
protection cut-out operates 3 consecutive
times within 3 minutes after startup.
Lit
Once
A thermistor shorts or opens during
compressor running.
Lit
Once
Lit
Twice
Lit
3 times
Lit
4 times
Lit
9 times
Once
Not lit
18A (MXZ-2C20NA2)/21 A (
Lit
Lit
The discharge temperature exceeds 239°F (MXZ-
2C20NA2)/222.8°F (
Compressor can restart if discharge temperature
thermistor reads 176°F (MXZ-2C20NA2) 203°F
(
)/212°F (
or less 3 minutes later.
Lit
Lit
The outdoor heat exchanger temperature ex-
ceeds 158°F during cooling or the indoor gas
pipe temperature exceeds 158°F during heating.
3 times
Not lit
(
4 times
Not lit
The P.C. board temperature exceeds 152°F (MXZ-
4C36NA2)/189°F (
5C42NA2) during operation.
Lit
Lit
A failure occurs 3 consecutive times within
30 seconds after the fan gets started.
Lit
5 times Nonvolatile memory data cannot be read
properly.
Lit
Lit
The frequency of the compressor is kept 80
Hz or more and the discharge temperature is
kept under 102.2°F for more than 20 minutes.
Lit
6 times Communication error occurs between the out-
door control P.C. board and outdoor power P.C.
board for more than 10 seconds.
The communication between boards protec-
tion cut-out operates 2 consecutive times.
Lit
7 times A short or open circuit is detected in the cur-
rent sensor during compressor operating.
Current sensor protection cut-out oper-
ates 2 consecutive times.
5 times
Not lit
Zero cross signal cannot be detected
while the compressor is operating.
The protection cut-out of the zero cross de-
tecting circuit operates 10 consecutive times.
5 times
Not lit
A failure is detected in the operation of the
converter during operation.
5 times
Not lit
The bus-bar voltage exceeds 400 V or
falls to low level during compressor oper-
ating.
Lit
Lit
The indoor unit detects an abnormality in
the LEV and drain pump.
81
TROUBLESHOOTING CHECK TABLE (11-4.).
• Check the connection of the com-
pressor connecting wire.
• Refer to 11-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
• Refer to 11-6.
thermistors".
• Replace the outdoor control P.C. board.
• Refer to 11-6.
thermistors".
• Reconnect compressor connector.
)/28 A (
• Refer to 11-6.
verter/compressor".
• Check the stop valve.
• Check refrigerant circuit and refrig-
erant amount.
)/240.8°F (MXZ-2C20
• Refer to 11-6.
) during operation.
)
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
)/192°F
• Check around outdoor unit.
) during operation.
• Check outdoor unit air passage.
• Refer to 11-6.
fan motor".
• Refer to 11-6.
fan motor".
• Replace the outdoor control P.C.
board.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6.
• Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
• Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
• Check the voltage of power supply.
• Replace the outdoor power P.C.
board.
• Check the voltage of power supply.
• Replace the outdoor power P.C. board
or the outdoor control P.C. board.
• Refer to 11-6.
• Check the drain pump of the indoor unit.
Indoor/
outdoor unit
Remedy
failure mode
recall function
"Check of outdoor
"Check of outdoor
"How to check in-
"Check of LEV".
"Check of outdoor
"Check of outdoor
"Check of LEV".
"Check of LEV".