Flow Chart Of The Detailed Outdoor Unit Failure Mode Recall Function; Releasing The Failure Mode Recall Function; Deleting The Memorized Abnormal Condition - Mitsubishi Electric MUZ-FS06NA Service Manual

Outdoor unit
Hide thumbs Also See for MUZ-FS06NA:
Table of Contents

Advertisement

2. Flow chart of the detailed outdoor unit failure mode recall function

Operational procedure
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 77°F (25°C). *1
Does the left lamp of the OPERATION INDICATOR lamp
on the indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the left
lamp of the OPERATION INDICATOR lamp.
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
the outdoor unit failure mode table (10-2.3.).
Make sure to check at least 2 consecutive blinking cycles.

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.

Deleting the memorized abnormal condition

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
*2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF
ON
OFF
OBH873
2
*
Yes
(Blinks
)
2
*
Repair the failure parts.
Blinking at 0.5-
3-second ON
second interval
No beep
Beeps
Repeated cycle
1. Regardless of normal or abnormal condition, 2 short
*
beeps are emitted as the signal is received.
No
(OFF)
The outdoor unit is normal.
Release the failure mode recall function accord-
ing to the left mentioned procedure.
2.5-second OFF
3-second ON
No beep
Repeated cycle
27
Blinking at 0.5-
second interval
Beeps
Repeated cycle