Removing The Expansion Valve; Before Using The Service Point (High Pressure Side) - Mitsubishi Electric MXZ-2C20NA2-U1 Service Manual

Outdoor unit
Hide thumbs Also See for MXZ-2C20NA2-U1:
Table of Contents

Advertisement

OPERATING PROCEDURE
NOTE: Gas recovery is not required if the unit is pumped down.
(1) Remove the top panel and the service panel (Refer to
section 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove all the LEV coils.
(4) Detach all the brazed parts of the expansion valves and
pipes.
(1) Remove the service panel (Photo 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove the top panel, the cabinet, and the back panel
(Photo 1, 2, 3).
(4) Disconnect all the connectors and the lead wires on the
outdoor control P.C. board.
(5) Remove all the screws of outdoor control P.C. board holder,
and remove the outdoor control P.C. board holder (Photo 5).
(6) Make sure that the service port is visible.
OBH702G
Photo 11
LEV coils
Photo 12
Service port
(High pressure side)
105
Expansion
valves