Outdoor Unit Failure Mode Table - Mitsubishi Electric MXZ-2A40VA Service Manual

Split-type, heat pump air conditioners outdoor unit
Hide thumbs Also See for MXZ-2A40VA:
Table of Contents

Advertisement

2. Outdoor unit failure mode table

MXZ-2A
The left lamp of
Abnormal point
OPERATION INDICAOR
(Failure mode / protection)
lamp(Indoor unit)
None(Normal)
OFF
Outdoor power system
2-time flash
3-time flash
Discharge temperature
thermistor
Defrost thermistor
Ambient temperature thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
Outdoor heat exchanger
temperature thermistor
Over current
4-time flash
Compressor
5-time flash
Discharge temperature
High pressure
6-time flash
Fin temperature
7-time flash
P.C. board temperature
8-time flash
Outdoor fan motor
9-time flash
Nonvolatile memory data
Discharge temperature
10-time flash
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (13-4.).
LED indication
Condition
(Outdoor P.C. board)
LED 1
LED 2
-
-
Lighting Lighting
When over current protection stop is
continuously performed three times
within 1 minute after the compressor
gets started, or when converter
protection stop or bus-bar voltage
protection stop is continuously
performed three times within 3
minutes after start-up.
Lighting Once
When thermistor shorts or opens
during compressor running.
Lighting Once
Lighting Twice
Lighting 3 times
Lighting 4 times
Lighting 9 times
Once Goes out
When 28A current flow into intelligent
power module.
The possibility of intercepting the
Twice
Goes
overcurrent by the compressor lock is
out
high.
9 times
Goes
The compressor doesn't synchronize
out
with the operating power.
When discharge temperature exceeds
Lighting Lighting
116:
during operation.
Compressor can restart if discharge
temperature thermistor reads 100: or
less 3 minutes later.
Lighting Lighting
When the outdoor heat exchanger
temperature exceeds 70:
during cooling or the indoor gas
pipe temperature exceeds 70:
during heating.
3 times
Goes
When the fin temperature exceeds
out
87: during operation.
4 times
Goes
When the P.C. board temperature
out
exceeds 70: during operation.
Lighting Lighting
When failure occurs continuously
three times within 30 seconds after
the fan gets started.
Lighting 5 times
When nonvolatile memory data
cannot be read properly.
Lighting Lighting
When the frequency of the
compressor is kept 80Hz or
more and the discharge
temperature is kept under 39:
for more than 20 minutes.
54
Indoor/outdoor
Correspondence
unit failure mode
recall function
• Check the connection
of the compressor
connecting wire.
• Refer to 13-4.E
"How to check
inverter / compressor".
• Check the stop valve.
• Refer to 13-6.F "Check
of outdoor thermistors".
• Replace the outdoor
electronic control
P.C. board.
• Refer to 13-6.F "Check
of outdoor thermistors".
• Reconnect compressor
connector.
• Refer to 13-6.E "How to
check inverter/
compressor".
• Check the stop valve.
• Check the connection of
the compressor
connecting wire.
• Refer to 13-6.E "How to
check inverter/
compressor".
•Check refrigerant circuit
and refrigerant amount.
• Refer to 13-6.D "Check
of LEV".
•Check refrigerant circuit
and refrigerant amount.
• Check the stop valve.
• Check around outdoor
unit.
• Check outdoot unit air
passage.
• Refer to 13-6.G "Check
of outdoor fan motor".
• Refer to 13-6.G "Check
of outdoor fan motor".
• Replace the outdoor
electronic control
P.C. board.
•Check refrigerant circuit
and refrigerant amount.
• Refer to 13-6.D "Check
of LEV".

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents