Honeywell CentraLine CLIOL822A Product Data page 3

Lonworks bus i/o modules
Table of Contents

Advertisement

Analog Input
Module
CLIOL821A
no. of I/Os
8 analog inputs
characteristics Linear Graph, 0...10 VDC with pull-
up, 0(2)...10 VDC without pull-up
NTC20kΩ (-50...+150 °C, default)
NTC10kΩ (-30...+100 °C)
PT
(-50...150 °C)
1000-1
PT
(0...400 °C)
1000-2
Johnson A99 PTC (-40...+120 °C)
(-30...+130 °C)
NI1000TK5000
PT
(-50...150 °C)
3000
BALCO
(-30...120 °C)
500
Also configurable as:
binary inputs
 Linear graph (0...10 V with pull-up)
Features:
 16-bit resolution
 configurable offset per input
 auxiliary voltage: 10 VDC, I
5 mA
Manual Overrides as per EN ISO 16484-2:2004
The manual override switches and potentiometers of the output modules support direct operation as per EN ISO 16484-
2:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently
of the controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the
corresponding output LED will blink continuously, and the output module will send a feedback signal with the status
"manual override" and the given override position to the controller (which will then also store this information in its alarm
memory).
NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Table 3. Pluggable LonWorks Bus I/O Module specifications
Analog Output
CLIOL822A, CLIOLR822A
8 analog outputs
0...11 VDC /  1 mA
Also configurable as: floating
outputs or binary outputs (0 V
/ 10 V)
Features:
 8-bit resolution (default)
 Safety position (remain, 0%,
50%, 100%)
 red LED per output
 light intensity follows output
level in auto
Version with manual
override (R):
 1 potentiometer per output
 auto feedback signal (mode
+ value)
=
 blinking in manual override
max
position
LONWORKS BUS I/O MODULES – PRODUCT DATA
Binary Input
CLIOL823A
12 binary inputs
requiring a gold contact
or open collector
static binary input,
(default: dry contact)
Also configurable as:
totalizers (20 Hz)
Features:
 1 LED per input
 Color mode can be
set per input to
OFF/yellow or
green/red using
CARE / COACH AX /
COACH NX
 ON: < 1.6 kΩ to GND
or < 2.5 V to GND,
OFF: > 90 kΩ to
GND or > 4 V to
GND
3
Relay Output
CLIOL824A, CLIOLR824A
6 relay outputs
relay outputs (default)
Features:
 Changeover relays
 Voltage: 19...250 VAC,
1...29 VDC, P>50 mW
 max. total current: 12 A
 current per relay: N.O.: 4(4) A
(AC) or 4(1) A (DC),
N.C.: 2(1) A (AC) or 4(1) A
(DC)
 Safety position (remain, 0%,
100%)
 yellow LED per output
Version with manual override
(R):
 1 switch per output
 auto feedback signal (mode +
value)
 blinking in manual override
position
EN0Z-0980GE51 R0119