LONWORKS BUS I/O MODULES – PRODUCT DATA

Binary Input Module

1
Fig. 15. CLIOP823A
L
W
ON
ORKS
XS823 terminal socket)
Legend
1
L
W
service button S1
ON
ORKS
2
Status LEDs
3
Service LED
4
Power LED
NOTE: The hex switch S2 (located next to the L
service S1) has no function in combination with a
L
W
Bus I/O module. It is used with Panel
ON
ORKS
Bus I/O modules, only.
The CentraLine L
W
ON
ORKS
binary inputs, is installed with the XS823 or XSU823 Terminal
Socket.
Configuration as Fast Totalizer
Using CARE / COACH AX / COACH NX, the binary inputs
can be configured as fast totalizers for operation in con-
junction with devices equipped with an open collector output.
Table 5. Binary inputs used as fast totalizers
Frequency
max. 20 Hz
min. 25 ms
Pulse ON
Pulse OFF
min. 25 ms
Bounce
max. 5 ms
EN0Z-0980GE51 R0119
3 4
2
Bus BI Module (shown with
W
ON
ORKS
Bus Binary Input Module, with 12
BI
GND
FAST
TOTALIZER
Fig. 16. Configuration of a binary input as a fast totalizer
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
2 3
5
1
4
GND GND GND GND GND GND GND GND GND GND GND GND
13
15
16
18 19 20 21 22 23 24
14
17
Fig. 17. CentraLine L
ON
Features
Static binary input (dry contact)
Totalizer for up to 20 Hz
LEDs per binary input supporting alarm display mode
(red/green) or status mode (off/yellow).
Color mode of each LED can be set to OFF/yellow or
green/red in CARE / COACH AX / COACH.
12
+V
18 VDC (NOT STABILIZED)
10 kOHM
150 kOHM
DRY CONTACT
4 ... 40 VDC = OPEN
0 ... 2 VDC = CLOSED
6
7
8 9 10 11 12
W
Bus Binary Input Modules
ORKS
(schematic)
COM
75
A
COM
76
B
24
77
V~
24
78
V~0
25 26