Honeywell CentraLine CLIOL822A Product Data page 17

Lonworks bus i/o modules
Table of Contents

Advertisement

Approvals, Certifications, and Standards
Approvals and Certifications
CE-approved
Conforms to EN 60730-1 and EN 60730-2-9
Investigated according to United States Standard
UL916 (USL-listed) as well as according to Canadian
National Standard(s) C22.2 (CNL-listed)
Classification according to EN60730-1
Environmental conditions:
Pollution degree:
Protection against shock:
Software class:
Overvoltage category:
Classification according to EN60529
(Degree of Protection Provided by Enclosures)
Classification:
Ambient Environmental Limits
Operating temperature:
Storage temperature:
Humidity:
Current Requirement and Heat Dissipation
The L
W
Bus I/O Modules are equipped with highly-
ON
ORKS
efficient switching power supplies which provide for relatively
uniform power consumption over a wide range of supply
voltages (see Table 6). The specific heat dissipation inside
the modules amounts to less than 2 W for all models.
Table 6. Current requirements at nominal voltage
devices powered
CLIOL821A
CLIOL822A, CLIOLR822A
CLIOL823A
CLIOL824A, CLIOLR824A
Mechanical
Housing Dimensions (H x W x D)
The L
W
Bus I/O Modules (mounted on Terminal
ON
ORKS
Sockets) all have the dimensions: 110 X 90 X 93 mm (see
also Fig. 23 on page 18).
Housing Material
Plastic, flame-retardant
Mounting Methods
DIN-rail mounting (e.g., in control cabinet).
Calculated Lifetime of Weakest Components
MTBF  13.7 years (under typical operating conditions)
For use in home (residential,
commercial, and light-industrial)
environments
Class 2
Class II
Class A
II
IP20
0 ... +50 °C at 5...93% r.H.
-20 ... +70 °C at 5...93% r.H.
5 ... 93% r.h. non-condensing
supply voltage
24 VAC
24 VDC
130 mA
80 mA
150 mA
90 mA
180 mA
130 mA
140 mA
80 mA
LONWORKS BUS I/O MODULES – PRODUCT DATA
17
EN0Z-0980GE51 R0119

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents