Redundant Automation Units - Siemens SICAM AK Manual

Rtus. redundancy,
Table of Contents

Advertisement

1.3

Redundant Automation Units

Connection between both BSEs over HSL:
The High Speed Link (HSL) is used for the synchronization of both redundant BSEs
(C-CPUs).
In the case of AU redundancy the HSL is established with a fiber optic cable.
Exception: If the distance between both AUs is more than 200 m, in all cases the redundancy
synchronization must take place over a separate fast data connection.
That causes a high load in the AU. Therefore take the following into consideration:
Parameterize a connection between both AUs on that PRE, that is to be responsible for
the synchronization of both BSEs
The PRE for this data connection must be coupled to that BSE which is to be
synchronized.
Use cycle times that are long enough for your CAEx plus application
Make sure, that both BSEs have an identical configuration and that they are loaded with
the same FW revision and the same parameters (state).
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
Unrestricted
Redundancy via SCA-RS
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents