2.4.2.3.3
Reload Default Parameters
For reloading default parameters, remove the SD card from the (de-energized) CP-6010.
With a SD card write/read device, copy the file Par.bin from the folder Reset_Param to the
folder Param.
After that, insert the SD card again into the CP-6010 and supply that with power.
2.4.2.3.4
Load Updated Firmware
For working with the existing parameters with a new firmware version, remove the SD card
from the (de-energized) CP-6010.
With a SD card write/read device, copy the latest firmware into the root directory and delete
the file Par.bin from the folder Param.
After that, insert the SD card into the CP-6010 and supply that with voltage. All the previous
parameters will be copied now from the flash memory of CP-6010 to the SD card.
2.4.3
Time Settings
The time settings reside within the menu Time Setting | Time.
2.4.3.1
Local Time Set
If in the SICAM AK Redundancy system no NTP server is used, the time setting can be
performed locally.
Select thereto under the item "Local time set" the correct date and time via the relevant pull-
down menu to update the device time. By default, the time of the engineering PC is displayed.
The settings are stored by clicking the button Apply and are updated instantly (no reset is
required).
Note
With usage of a NTP server for the time synchronization, the local time setting is disabled.
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
Unrestricted
Redundancy via CP-6010