11.2

Telegrams

11.2.1 Diagnosis of AS-i safety monitor
State of output circuits, operating mode
Notice!
The alternate sending of data calls (0) and (1) is essential for consistent data
transmission. See "Diagnostic procedure" on page 99.
The binary values of the data calls relate to the AS-interface level and may
possibly be inverted at PLC level.
Data call / Value
(0) / 1111
State of monitor
Data call / Value
(1) / 1110
Store diagnostic
information (state
of monitor)
Answer
Meaning
D3 ... D0
0000
Protective operation, everything OK
(unavailable, unconfigured or dependent output circuits are
displayed as OK).
0001
Protective operation, output circuit 1 off.
0010
Protective operation, output circuit 2 off.
0011
Protective operation, both output circuits off.
0100
Configuration operation: Power On.
0101
Configuration operation
0110
Reserved / not defined
0111
Configuration operation, fatal device error,
RESET or device exchange required.
1XXX
No up-to-date diagnostic information available, please
wait.
Answer
Meaning
D3 ... D0
1000
Protective operation, everything OK
(unavailable, unconfigured or dependent output circuits are
displayed as OK).
1001
Protective operation, output circuit 1 off.
1010
Protective operation, output circuit 2 off.
1011
Protective operation, both output circuits off.
1100
Configuration operation: Power On.
1101
Configuration operation
1110
Reserved / not defined
1111
Configuration operation, fatal device error,
RESET or device exchange required.