IFM Electronic Ecomat 300 AC422S Original Device Manual page 66

Fail-safe smartplc ac4s with ethernet/ip interface, for iso 13849 up to pl e, for iec 62061 up to sil cl 3
Table of Contents

Advertisement

ifm
Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2
Operation
>
Slave status: colour code + symbols
Single slave
A/B slave
>
Meaning of the colour combinations (example: configuration error type 2)
Symbol
Colour
grey red
grey
grey
grey red
grey red
66
Colour
Meaning
grey
No slave found:
slave address is neither in the LPS nor in the LDS
green
Slave is activated ( in LAS)
red
Configuration error type 1:
– slave is projected (in LPS) but was not found (in LDS)
yellow
Slave signals a peripheral fault
pink
Several slaves have the same address (double address error)
grey red
Configuration error type 2:
– the found slave (in LDS) is not projected (in LPS)
– the found slave has another profile than projected
Meaning
Configuration error type 2:
– Single slave is projected (in LPS) but was not found (in LDS).
– Instead, a new A slave with the same address was installed.
Configuration error type 2:
– Single slave is projected (in LPS) but was not found (in LDS).
– Instead, a new B slave with the same address was installed.
Configuration error type 2:
– A or B slave is projected (in LPS) but was not found (in LDS).
– Instead, a new single slave with the same address was installed.