Explicit Message; System Configuration On Plc - YOKOGAWA SmartDac + GX10 User Manual

Ethernet/ip communication (/e1)
Hide thumbs Also See for SmartDac + GX10:
Table of Contents

Advertisement

Explicit Message
System Configuration on PLC
IM 04L51B01-18EN
An Explicit message is a point-to-point, request/response-type communication.
Use the configuration tool to code an Explicit message as an MSG instruction in the
control logic. In the MSG instruction, set all the information including a target device,
target register, and read/write. Download the created control logic to a PLC and execute
it.
On the recorder the data count to be accessed per MSG instruction should be 100 or less.
In Case of PLC-2, PLC-5, and SLC
• Commands
When creating an MSG instruction, specify a command. The recorder supports the
following commands:
Target PLC
PLC-2
PLC-5
SLC
• Specification of data to be accessed
Specify which of the data in the recorder should be accessed. The PLC-2, PLC-5, and
SLC manage data to be accessed in units of "files."
Command: PLC2 Unprotected Read/Write
Data to be accessed
Type
Input/Output channel
(GX/GP main unit)
(GM main unit)
Command name
PLC2 Unprotected Read/Write
PLC5 Word Range Read/Write
PLC5 Typed Read/Write
SLC Typed Read/Write
File number
Number
Data type: INT16
0001
1000
• • •
• • •
0050
1049
0101
1050
• • •
• • •
0150
1099
0201
1100
• • •
• • •
0250
1149
0301
1150
• • •
• • •
0350
1199
0401
1200
• • •
• • •
0450
1249
0501
1250
• • •
• • •
0550
1299
0601
1300
• • •
• • •
0650
1349
0701
1350
• • •
• • •
0750
1399
0801
1400
• • •
• • •
0850
1449
0901
1450
• • •
• • •
0950
1499
Continued on next page