8.5.2 Alarm description

8.5.2.1 Overvoltage alarm
ACTIVATION
The overvoltage alarm is activated if the voltage reading of the R5 Controller is above the value defined by
parameter Overvoltage alarm threshold
Chap. 7.5.2
alarm delay
MANAGEMENT
The activation of the overvoltage alarm triggers the "slow" disconnection of all banks, one at a time, and with a
delay between them equal to P.4
automatic power factor correction mode for all the inserted banks whose Step n function (n=1,2,3,4,5)
"
"
"
been set to
CAP
or
correction mode
) for all the banks whose status has been set to "ON".
At the same time, the relay outputs set as "ALA" and associated to the "THHV" or "ALL" alarm will be activated
unless parameter P.25
operating conditions.
DISPLAYING
The Controller will stay in the above-mentioned screen until:
- key
is pressed for more than 2sec (the alarm is anyway active);
- alarm is deactivated or manually reset by the operator.
Afterwards, the Measurement Menu will be automatically displayed and will show, respectively:
- the cosphi value and the alarm icon on the top left. The alarm will be anyway active in the Current Alarm Menu
Chap. 8.5.1
(
);
- the cosphi value, but not the alarm icon.
If, parameter P.25
operating conditions, the previous screen will be temporarily displayed for 3sec. The alarm will then automatically go back
to the first screen of the Measurement Menu by displaying the cosphi value, but not the alarm icon. The alarm will be
anyway present in the Current Alarm Menu.
STATISTICS
The alarm counter will be increased in the Statistics Menu (
DEACTIVATION
The alarm is automatically deactivated if the voltage reading of the R5 Controller is below the value defined by
parameter Overvoltage alarm threshold
Chap. 7.5.2
alarm delay
RESET
Alarm can be manually reset from the Current Alarm Menu by pressing key
"
Current alarm reset =
MU-MID-R5-D-ENG.doc
Chap. 7.5.1
.
Transient time during disconnection (
"
ON
and in manual power factor correction mode (refer to

Alarm masking management (

Alarm masking management (
Chap. 7.5.1
.
"
Chap. 7.6
ON
, refer to
).
for a time (in sec) equal to the value of parameter Overvoltage
Chap. 7.6
) has been set to mask the alarms under defined
Independent of the current displaying, the alarm will be indicated
with the displaying of the relevant page of the Current alarm menu
that will be alternately shown with the numerical value
corresponding to the maximum voltage value measured since
alarm activation (450V in the example shown).
Chap. 7.6
) has been set to mask the alarms under defined
Chap. 8.4
) at every occurrence.
for a time (in sec) equal to the value of parameter Overvoltage
Chap. 7.6
). This process takes place in
Chap. 8.8 - Manual power factor
(function possible only if P.13
Chap. 7.2.5
has