7.1.8 VT secondary winding

The default value is "400". The permitted ranges for the parameter are [210÷250] and [370÷430].
Example: if the transformer size is 690/400, enter the "400" value.
NOTE: if the VT is not present, set the supply voltage value used for the Power Factor Controller (400 or 230).
If a permitted value is entered, the controller will move to the next parameter setting screen (Voltage reading
phase).
7.1.9 Voltage reading phase
The default value is "L23". The possible permitted values for the parameter are [L1n; L2n; L3n; L12; L23; L31].
Example 1: if the power supply (or the VT) was connected between the phases S and T, select the value
Example 2: If the power supply (or VT) was connected between the R phase and the neutral, select the value
After parameter is confirmed, the controller will move to the next parameter setting screen (Capacitor nominal
voltage).