7.2.3 Re-connection time

The default value is "60". The permitted range for the parameter is [1÷600]sec.
Example: if the discharge time of the capacitor banks is 60sec, set the value "60".
WARNING: the Re-connection time parameter must be set consistently with the indications given in the power
factor correction equipment manual. Entering a time shorter than the recommended one can lead to equipment and/or
controller damage.
If a permitted value is entered, the controller will move to the next parameter setting screen (Switching manoeuvre
time).
7.2.4 Switching manoeuvre time
The default value is "60". The permitted range for the parameter is [1÷30000]sec.
Set a lower value if the reactive power to be corrected quickly varies. Set a higher value if the reactive power to be
corrected slowly varies.
Example: to set a switching manoeuvre time of 9000sec, enter:
If a permitted value is entered, the controller will move to the next parameter setting screen (Step 1 function).
7.2.5 Step n function (n=1,2,3,4,5)
By scrolling the Setup Menu for each relay output (1 to 5) there are a first page for function definition (Step n
function) and a second page for further parameter specification (Step n power or Alarm n) based on the selected
function.
NOTE: the images and the description below show the Step 1 function parameter, i.e. all what can be applied for all
steps with n index with n = 1,2,3,4,5.
The default value is "CAP". The possible permitted values for the parameter are [CAP; OFF; ON; ALA].
Select the "CAP" value for an output connected to a capacitor bank that you want to be automatically piloted by the
controller.