Operation

Operation of the controller can take place via data communication
or from a separate display.
The buttons (EKA 162 only)
When you want to change a setting, the two buttons will give you
a higher or lower value depending on the button you are push-
ing. But before you change the value, you must have access to the
menu. You obtain this by pushing the upper button for a couple of
seconds - you will then enter the column with parameter codes. Find
the parameter code you want to change and push the two buttons
simultaneously. When you have changed the value, save the new
value by once more pushing the two buttons simultaneously.
Or briefly:
Gives access to the menu (or cutout an alarm)
Gives access to changes
Saves a change

Temperature setting

When it is the temperature setting you wish to change, do not enter
the menu. Push both buttons simultaneously and you will be al-
lowed to change the temperature reference when the display an-
swers back by flashing.
Forced control
In addition to the normal way of operating the controller you are
now able to perform a number of forced control functions which
you start, as follows:
- Cut out alarm relay / check alarm code
• Push the upper button
- Read the defrost stop temperature
• Push the lower button
- Manual start or stop of defrost
• Push the lower button for four seconds
Examples put in another way:
Set the temperature
1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
Set a menu
1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to
change
3. Push both buttons simultaneously until the parameter value is
shown
4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting
8
English
Instructions RI8JN253 © Danfoss 05/2005

Menu survey

Function
Normal display
Shows the temperature at the selected sensor
Define view in O17
If you wish to see selected defrost stop
temperature, give the lower button a brief
push (1 sec.)
no= stop on temperature not selected
Thermostat
Differential
Max. limitation of thermostat's setting tem-
perature
Min. limitation of thermostat's setting tem-
perature
Temperature unit (°C/°F)
Correction of signal from S4 (S
)
out
Correction of signal from S3 (S
)
in
Start/Stop of refrigeration
Reference displacement during night opera-
tion
Define thermostat function
1=ON/OFF, 2=Modulating
Definition and weighting, if applicable, of
thermostat sensors
100%=S4 (S
), 0%=S3 (S
).
out
in
The thermostat temperature can be seen in
U17
Time between melt periods
Duration of melt periods
Alarm
Alarm time delay
Door alarm time delay
Time delay during cooling
High alarm limit
Low alarm limit
Setting of the weighting between S3/S4 to
be used by the alarm function. The alarm
temperature can be seen in u57
Compressor
Min. ON-time
Min. OFF-time
Defrost
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Time displacement of defrost cut-ins during
start-up
Drip-off time
Fan start delay after defrost
Fan start temperature
Fan cut-in during defrost (yes/no)
Defrost sensor
0=S4 (S
) , 1=S5 (S
), 2=non. Stop on time
out
def
Defrost at power up
RTC module (if installed)
see RTC instructions
Injection control function
Max. value of superheat reference
Min. value of superheat reference
MOP temperature
AKV valve's time period
Should only be changed to OFF by trained
staff
Adaptive control
Should only be changed to OFF by trained
staff
SW = 1.0x
Para
Factory
Min.
Max.
meter
settings
-
°C
-
°C
r01
0.1 K
10.0 K
2.0
r02
-49°C
50°C
50.0
r03
-50°C
49°C
-50.0
r05
°C
°F
0/°C
r09
-10.0 K 10.0 K
0.0
r10
-10.0 K 10.0 K
0.0
r12
OFF
ON
OFF
r13
-20.0 K 20.0 K
0.0
r14
1
2
1
r15
0%
100%
100
r16
0 h
10 h
1
r17
0 min
10 min. 5
A03
0 min. 120 min 30
A04
0 min. 90 min. 60
A12
0 min. 240 min 120
A13
-50°C
50°C
5.0
A14
-50°C
50°C
-30.0
A36
0%
100%
100
c01
0 min
50 min 0
c02
0 min
50 min 0
d02
0
25°C
6.0
d03
OFF
48 h
8
d04
0
180 min 45
d05
0
240 min 0
d06
0
60 min 0
d07
0
60 min 0
d08
-15
0°C
-5.0
d09
no
yes
no
d10
0
2
2
d13
no
yes
no
t01 to
t16
n09
3.0 K
15.0 K
12.0
n10
3.0 K
10.0 K
3.0
n11
-50.0°C 15°C/off 15°C
n13
3 sec.
6 sec.
6
n14
OFF
ON
on
EKC 414A1