fafnir SEPARIX-Control CT Technical Documentation Manual page 19

Hide thumbs Also See for SEPARIX-Control CT:
Table of Contents

Advertisement

Install the measuring transducer in accordance with the connection diagram on the inside
of the device cover.
Observe the maximum operating parameter values specified in the connec-
tion diagram (see Figure 6).
(1)
Check the configuration of the measuring transducer and correct if necessary (see
section 4.2).
(2)
Whichever applicable, connect the SEPARIX-C L Plus interface sensor to the meas-
uring transducer according to the connection diagram.
(3)
Whichever applicable, connect the SEPARIX-T L Plus high-level sensor to the
measuring transducer according to the connection diagram.
If a shielded cable is used, this must be earthed in accordance with na-
tional or local installation rules and regulations.
(4)
Whichever applicable, connect external alarm devices to the terminals 6 to 8 (in-
terface relay output) and 9 to 11 (high level relay output) of the SEPARIX-Control
CT measuring transducer.
(5)
Connect the measuring transducer to an auxiliary power unit of 230 V
using the terminals marked PE/N/L. The green "Power" LED of the SEPARIX-Control
CT blinks. The warning system is operational.
The SEPARIX-Control CT measuring transducer with a connected
SEPARIX-T L Plus high-level sensor is only operational after the sensor
has heated up. According to the ambient temperature this heating phase
can last up to 2 minutes.
(6)
Inform owner and/or system operator about the purpose of the warning system
and, where applicable, of any additional alarm transmitters that have been con-
nected. Point out all aspects specific to the present arrangement, particularly if the
measuring transducer's default factory settings have been changed (e.g.
acknowledge button disabled). Also instruct them how to act in the event of a fault
or an alarm (e.g. acknowledge alarms and faults, customer service phone no. in the
event of an alarm, etc.).
SEPARIX-C/-T and SEPARIX-Control CT
, 50/60 Hz,
AC
Page 16/37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Separix-c l plusSeparix-t l plus

Table of Contents