A system test is only possible if the SEPARIX-T L Plus high-level sensor
has been heated up.
If the test button is pressed alone, an unacknowledged alarm will be sim-
ulated. If both the test and acknowledge buttons are pressed
simultaneously, an acknowledged alarm will be simulated.
The test button does not replace the function test of the warning system
(see section 5).
The measuring transducer configuration settings allow both buttons to be locked, e.g. in
cases where the measuring transducer is part of a central control system and the system
operator shall not acknowledge any faults or carry out any tests (see section 4.2).
4.2

Configuration

The measuring transducer is factory preconfigured and ready for operation. With the help
of the "Options" DIP switch you are able to configure SEPARIX-Control CT (see following
table):
Option
1
SEPARIX-C ...
2
SEPARIX-T ...
3
Relay energised
4
Relay acknowledgeable
5
Alarm delay
6
Acknowledge button
7
Test button
8
Alarm buzzer
* : Default factory setting
Table 1: SEPARIX-Control CT, configuration
Page 13/37
DIP switch OFF
OFF
OFF
Alarm *
Yes *
60 sec. *
Locked
Locked
Locked
DIP switch ON
ON *
ON *
No alarm
No
No
Unlocked *
Unlocked *
Unlocked *
SEPARIX-C/-T and SEPARIX-Control CT