Activation Of Separix-C; Activation Of Separix-T; Relay Energised; Relay Acknowledgeable - fafnir SEPARIX-Control CT Technical Documentation Manual

Hide thumbs Also See for SEPARIX-Control CT:
Table of Contents

Advertisement

Figure 6: SEPARIX-Control CT, terminals and "Options" DIP switch
4.2.1

Activation of SEPARIX-C

With switch 1, the SEPARIX-C L Plus interface sensor is activated. The Power LED indicates
whether the sensor is activated or deactivated (see section 4.1.1). The sensor is activated
by default.
Whenever both sensors will be deactivated, the device is no longer oper-
ational and the Power LED (see Figure 5) is OFF.
4.2.2

Activation of SEPARIX-T

With switch 2, the SEPARIX-T L Plus high-level sensor is activated. The Power LED indicates
whether the sensor is activated or deactivated (see section 4.1.1). The sensor is activated
by default.
Whenever both sensors will be deactivated, the device is no longer oper-
ational and the Power LED (see
4.2.3

Relay energised

With switch 3, it is configured whether the relay is energised in case of a fault/alarm or if it
is energised in normal operation. By factory default the relay is set energised in case of a
fault/alarm.
4.2.4

Relay acknowledgeable

With switch 4 the relay is configured whether it can be acknowledged and reset in case of
a fault/alarm with the red acknowledge button. Otherwise, the relay is reset only, if the
cause of the fault/alarm is corrected. By factory default the relay is set acknowledgeable.
SEPARIX-C/-T and SEPARIX-Control CT
) is OFF.
Figure 5
Page 14/37