STATIC PRESSURE SETTING

NOTE:
• When the 2" filter is installed for the first time, the static
pressure of the IDU must be adjusted.
• This is a one time setting. No setting is required when the
filter is replaced.
CAUTION
If the set up is not done correctly, the air flow volume will
decrease and it can lower the performance of the unit.
Unit connected to the controller (non-
programmable) —
Setting must be performed from the remote controller:
1. Press and hold MODE and FAN at the same time for five
seconds to enter the parameter setting mode as shown in
Fig. 15.
1G code
Fig. 15 —Parameter Setting Mode
2. Press ROOM TEMP/SWING to select the 1G code to 10,
and press TEMP UP/TEMP DOWN to select the 2G
code to 3 (0.12 in WC) as shown in Fig 16.
Fig. 16 —Setting 1G and 2G Codes
3. Press OK or wait for 15 seconds to confirm the setting
automatically and exit parameter setting.
For more details, refer to the installation manual provided
with the non-programmable remote controller.
© Carrier Corporation 2018
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 18-40VMF2-01
2G code
Printed in U.S.A.
Form 40VMF2-1SI
Unit connected to the controller
(programmable) —
Setting must be performed from the remote controller:
1. Press and hold FAN and BACK at the same time for five
seconds to enter the interface for parameter settings.
2. Press TEMP UP/TEMP DOWN to move the cursor
down.
3. Choose STATIC PRESSURE as shown in Fig. 17.
ANTI COLD BLOW
TERMINAL FAN CONFIGURATION
THERMO-OFF FAN SPEED SEETING
OCCUPANCY SENSOR
Fig. 17 —Static Pressure
4. Press MENU/OK to enter this setting.
5. Press TEMP UP/TEMP DOWN to select the static
pressure.
6. Choose the parameter 0.12 IN. WC as shown in Fig. 18.
STATIC PRESSURE
0.12 IN.WC
Fig. 18 —Parameter 0.12 IN. WC
7. Press MENU/OK to confirm the setting.
For more details, refer to the installation manual provided
with the programmable remote controller.