• Connect the parallel CAT5E cables as a "Ring Network" (Figure 3) using the parallel kit plate to
fix them to the UPS rear panel (Figure 4)
2 units parallel
3 units parallel
4 units parallel
Figure 2
CAUTION
The maximum length of the communication connecting wires shall be less than 7M.
All the Input/ output power cable should have the same length (max 25m)
Figure 4
Daker DK 4.5-10 kVA
Figure 3
1050mm RJ-45
communication
connecting wire
1900mm RJ-45
communication
connecting wire
Max. 25M; all Input
Power cables shall
be with the same
lenght
1900mm RJ-45
communication
connecting wire