Chapter 3: Configuration and Commissioning
4. When you have completed the required maintenance tasks, press F2 (Exit) to
exit the wizard.
Table 9: The maintenance wizard
Menu
Enable/Disable
Filter Status
Input Test
Output Test
Enable/Disable
The configuration wizard
To use the configuration wizard:
1. Press F1 (Wizard) from the Main menu.
2. Select Configuration Wizard.
3. Press F3 (Next) to step through the menus included in the wizard (see
Table 10 below).
Press Enter to access a menu. From a menu, press F2 (Back) to return to the
wizard.
4. Press F3 (Apply) to apply configuration changes, and then press F2 (Exit) to
exit the wizard.
Table 10: The configuration wizard
Menu
Network Setup
Date and Time
Alarm Levels
Flow Setup
Inputs
40
Description
Disable devices before starting maintenance. See
"Disabling a device" on page 53 for more information.
Display the filter status for detectors. We recommend that
the filter is changed when the Filter value reaches 20% (this
indicates an 80% filter blockage). See "Detector status" on
page 42 for more information.
Test inputs. See "Performing an input test" on page 51 for
more information.
Test outputs. See "Performing an output test" on page 50
for more information.
Enable devices previously disabled for maintenance.
Description
Scan the network to find devices. See "Configuring the
network" on page 67 for more information.
Configure date and time settings See "Changing the date
and time" on page 54 for more information.
Configure alarm level settings for detectors See
"Configuring the alarm levels" on page 62 for more
information.
Configure flow limit values, fan speed, and power save
settings for detectors See "Configuring flow parameters" on
page 66 for more information.
Configure input settings See "Configuring the inputs" on
page 56 for more information.
ModuLaser Modular Aspirating Smoke Detector Installation Manual