Note messages advise you of the possible loss of time or effort. They describe how to avoid the loss. Notes are also used to point out important information that you should read. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 6
This symbol indicates the Safety ground studs. These are for grounding cable screens, etc., and should not be connected to 0V or signal earth. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Aspirating smoke detectors are unique in being able to provide a consistent level of protection in a very wide range of environments by continuously making minor adjustments to sensitivity. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Greater than 8 years (depending on environment) Dust separator (filter) replacement Greater than 5 years (depending on environment) intervals Laser lifetime (MTTF) Greater than 50 years Programming PC via RS-232 IP rating IP50 Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
(3) OK: Illuminates to show normal operation when there are no faults. The OK lamp will flash during the 15-minute FastLearn period when the detector is first learning about its environment. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Models and verifies the performance of the pipe network design. All pipework designs must be validated using PipeCAD. • Remote: Configures and monitors the detector. Contact your local distributor for more details on these applications. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
www.acornfiresecurity.com Chapter 2 Installation and configuration Summary This chapter provides information necessary to install and configure the detector system. Caution: This product must be installed and maintained by qualified personnel adhering to all local or national installation requirements and any other applicable regulations.
The unit should not be placed in close proximity to any equipment expected to generate high levels of radio frequency signals (such as radio alarms) or units generating high levels of electrical energy (such as large electric motors or generators). Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
No more than one air handling unit may be protected with one detector. In this application, ensure that the sampling pipe is raised clear of high velocity air in the immediate vicinity of the air intake grill on standoff posts as shown in Figure 5. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Typical uses are for air duct sampling and allowing the installation of the detector in under-floor or ceiling voids or when sampling from pieces of computer related equipment (see Figure 6 and Figure 7). Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 20
Set the detector address switches correctly detector. when used in a network. Use excessive force when fitting sampling pipes Ensure that the detector is properly grounded. as this may damage the detector. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
130 mm (5 in.). The screen should be terminated under the cable gland cap (as shown in Figure 8). Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 22
4. Connect a second wire from the Earth terminal to the docking station ground stud. Figure 4 on page 10 shows the location of the ground stud. 5. Connect the ground wires to the ground stud. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 23
Figure 10: APIC address (1) APIC address terminal (2) Not used Figure 11 on page 18 shows the power and signal connections to the docking station for connection to a single network cable. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
(see Figure 12 on page 19). The relays are of the volt-free type, with a maximum current capacity of 500 mA at 30 VDC. Connect the screen of the relay cables to the ground stud of the detector. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
The interface is set to a single address mode, the card appears as a single address on the SLC, and the detector status is read from that address. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Addresses chosen for detectors do not have to be consecutive or in a given order as long as they are all different. Table 3 below provides the address table for detectors. Table 3: Address table Address Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Removing the detector is the reverse of the installation process, leaving the pipework and wiring connections installed in the docking station (as shown in Figure 11 on page 18). See Figure 15 above. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Events can be viewed on a PC screen or downloaded to disk using Remote. When the detector event log is full (200 events have been logged) and a new event occurs, the oldest event in the log is deleted (first-in, first-out). Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
4. Ensure that all detectors in the network area are clear of faults (troubles) and alarms (if applicable). 5. Launch Remote on the computer, enter the access code, and select Function Settings. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 35
Warehouse with diesel trucks operating Medium Once per 10,000 years Warehouse with diesel trucks operating Once per 20,000 years Warehouse with diesel trucks operating Once per 100,000 years Warehouse with diesel trucks operating Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 36
Pre-Alarm and Fire alarm is reached. This test should be repeated at least three times with consistent results. Recommended smoke generating medium is simulated smoke or wire burner. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Smoke test to check detector operation and Fire relay connection Simulate a fault to check the Fault relay and connection Complete and file maintenance records Reconnect detector to fire panel if required Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
If years one and three are OK, go to five-year interval. The detector employs a self-monitoring, automatically-adjusting calibration for the system. The inspection only requires a periodic visual inspection for a detector fault indication and performing the detector sensitivity test function. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
“Direction of flow” label beside the filter slot. 5. Slide the cartridge all the way into place. 6. Replace the detector cover and screws and initiate a FastLearn routine. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
In this case, it would be necessary to lead a pipe from the exhaust to the protected area to ensure nominal flow. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 43
Open bore pipes are not recommended. Check that the high flow fault threshold is not set too low. In the case of intermittent fault indications, try increasing the flow fault delay time. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Declaration of Performance number 10-3519-360-0099 EN 54 EN 54-20: 2006 Product identification See model number on product identification label Intended use See product Declaration of Performance Essential characteristics See product Declaration of Performance Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
UL-certified products may also contain additional approvals (for example, FM3230). See the markings on the product identification label. The detector must be powered by a suitable power supply approved to UL/ULC and FM3230 standards. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Page 47
PipeCAD documentation). Commissioning smoke tests should be performed to ensure that the farthest sampling hole from the detector is capable of generating a fire alarm within 120 seconds of receiving smoke. Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...
Feet VRMS Volts root mean square HSSD High sensitivity smoke detector Hertz (frequency) Inches Liquid crystal display Light emitting diode Materials and Equipment Acceptance Division of the City of New York Stratos Micra 10 Aspirating Smoke Detector Installers Handbook www.acornfiresecurity.com...