ZIEHL-ABEGG Icontrol FXDM Series Operating Instructions Manual
ZIEHL-ABEGG Icontrol FXDM Series Operating Instructions Manual

ZIEHL-ABEGG Icontrol FXDM Series Operating Instructions Manual

Frequency inverter for 3 ~ fans
Table of Contents

Advertisement

Quick Links

english
Icontrol
FXDM
Frequency inverter for 3 ~ fans
Operating Instructions
Software version: D1334A Part.-No. B1000AA4 from version 2.37
L-BAL-E036-GB 1422 Index 008
Part.-No. 00154773-GB

Advertisement

Table of Contents
loading

Summary of Contents for ZIEHL-ABEGG Icontrol FXDM Series

  • Page 1 english Icontrol FXDM Frequency inverter for 3 ~ fans Operating Instructions Software version: D1334A Part.-No. B1000AA4 from version 2.37 L-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB...
  • Page 2: Table Of Contents

    Operating Instructions Icontrol – model series FXDM Content General notes ............. Structure of the operating instructions .
  • Page 3 Operating Instructions Icontrol – model series FXDM 5.12 Digital inputs (D1, D2) ..........5.13 Relay outputs (K1, K2) .
  • Page 4 Operating Instructions Icontrol – model series FXDM 9.9.2 PIN protection activate, PIN 1234 ........9.9.3 Save user settings restore with PIN 9090 .
  • Page 5 Operating Instructions Icontrol – model series FXDM 11.1.1 Measuring arrangement ......... . . 11.1.2 Voltage measurements .
  • Page 6: General Notes

    We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. ZIEHL-ABEGG SE is not liable for damage due to misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modifications.
  • Page 7: Product Safety

    Operating Instructions Icontrol – model series FXDM Safety instructions Danger due to electric current Warning of dangerous voltage or dangerous current. Information Important additional information and advice for user. Product safety The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable.
  • Page 8: Modifications / Interventions In The Device

    Use only genuine spare parts / genuine wearing parts / genuine accessories from ZIEHL-ABEGG.Th- ese parts were specifically designed for the device. There is no guarantee that parts from non-original sources are designed and manufactured in correspondence with load and safety requirements.
  • Page 9: Product Overview

    3 Product overview Operational area Icontrol is the type-line of Ziehl-Abegg frequency inverter for controlling one motor with for frequency innverter suitable isolation system and bearings. We expressly point out that controlling Ziehl-Abegg fans in parallel operation is not possible in this series without endangering the motors.
  • Page 10: Minimum Space Requirement

    Operating Instructions Icontrol – model series FXDM Mounting • Depending on the housing model cut off necessary cable inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Metal sheet housings are supplied with stoppers. Any cable ducts openings not used must be sealed! •...
  • Page 11: Electrical Installation

    Operating Instructions Icontrol – model series FXDM Electrical installation 5 Electrical installation Safety precautions Danger due to electric current • Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations.
  • Page 12: Harmonics Current For Devices ≥ 4 And ≤ 16 A

    Operating Instructions Icontrol – model series FXDM Electrical installation 5.2.4 Harmonics current for devices ≥ 4 and ≤ 16 A According to EN 61000-3-2 these devices are to be classified as “professional” devices. The application is therefore limited to use by trade, certain vocations or industries. Connection to a low voltage supply (public networks) is allowed insofar as this has been clarified with the respective energy supply company responsible.
  • Page 13: Residual-Current-Operated Protective Device

    Operating Instructions Icontrol – model series FXDM Electrical installation Residual-current-operated protective device Danger due to electric current For an installation of r.c.d. protection, it shall be observed that this must be of “universal- current sensitivity”. In accordance with EN 50 178, Section. 5.2. other types of current-operated protective devices may not be used.
  • Page 14: Signal Connection Or Sensor Connection To Analog Inputs (Analog In 1, Analog In 2)

    Operating Instructions Icontrol – model series FXDM Electrical installation Signal connection or sensor connection to analog inputs (Analog In 1, Analog In 2) The unit has 2 analog inputs: • E1 Analog In = terminals “E1” / “GND” (Analog In 1) •...
  • Page 15: Connection Of External Terminal Type Axg-1A(E)

    Operating Instructions Icontrol – model series FXDM Electrical installation 5.11 Connection of external Terminal type AXG-1A(E) An external terminal is required for starting-up and setting-up versions that do not have an integrated terminal. • Model AXG-1A, Part-No. 349034 for wall mounting •...
  • Page 16: Lon Bus System Is Possible Via Add-On Module

    Operating Instructions Icontrol – model series FXDM Electrical installation 16.04.2008 v_modbus_geraete_anschluss.vsd general example for MODBUS device connection The data line must be connected from one device to the next. No other type of wiring is allowed! Always use only two wires of one lead (twisted pair) for the connection. Examples for MODBUS connection Recommended wire types 1.
  • Page 17: Bypass Circuit

    Operating Instructions Icontrol – model series FXDM Electrical installation 5.16 Bypass circuit Please observe the following during bypass switching (controller shunt with mains voltage): • Mutual locking of mains contactor and bypass protection • Time delay of at least 1 second during switching •...
  • Page 18: Controls And Menu

    Operating Instructions Icontrol – model series FXDM Controls and Menu 6 Controls and Menu Main switch (only with ending "Q" in type designation) Switch position Switch position • • Device switched off Device switched on • • In this position lockable. For this press in white Continuous speed control lever and hang in padlock 27.04.2010...
  • Page 19: Menu Operation

    Operating Instructions Icontrol – model series FXDM Controls and Menu Menu operation Display after turning on the mains voltage. description for menu language English = “GB” (delivery status). Switch over between “Start” and *Actual value with Escape Example for mode 1.01 (speed controller).
  • Page 20: Menu Structure

    Operating Instructions Icontrol – model series FXDM Controls and Menu Menu structure PIN 0010 STOP ← ← ← ← User Service → → → → ▼ ▼ ▼ ▼ ▲ ▲ ▲ ▲ Start Info Setting Events Base setup P↓ ↑ ESC P↓...
  • Page 21: Base Setup

    Operating Instructions Icontrol – model series FXDM Base setup 7 Base setup Jumper for the input signal Jumper position factory setting for 0 - 10 V signal. For temperature sensors (TF..) or sensors with 4 - 20 mA bring the internal jumper for the external signal in the correct position.
  • Page 22: Select Operation Mode

    Operating Instructions Icontrol – model series FXDM Base setup Select operation mode Information Simple installation is possible through the selection of the preprogrammed mode of operation. This determines the basic function of the device; factory setting 1.01 = speed controller (activation via 0 - 10 V signal).
  • Page 23: Start-Up

    Operating Instructions Icontrol – model series FXDM Start-up Start-up Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2. Double check that all connections are correct. 3. The mains voltage must match the information on the rating plate. 4.
  • Page 24: Menu Overview Mode (Without Add-On Modules )

    Operating Instructions Icontrol – model series FXDM Start-up “Start” Switch Motor to ON in menu group ▲ Menu overview Mode 1.01 (without add-on modules ) Base Controller Motor Start Info Setting Events IO Setup Limits Diagnostic setup Setup Setup 2.7 A 0.0 Hz 50.0 Hz 1.01...
  • Page 25: Programming

    Operating Instructions Icontrol – model series FXDM Programming 9 Programming Speed controller 1.01 1.02 1.01 9.1.1 Base setup Base setup Base setup Mode Factory setting Mode: 1.01 Mode E1 Analog In Selection: 0 - 20 mA, 4 - 20 mA, Bus (Inverting IO Setup) Factory setting: 0 - 10 V E1 Analog In...
  • Page 26: Base Setup 1.02

    Operating Instructions Icontrol – model series FXDM Programming Diagram setting signal and output frequency [Hz] n-min 10 Hz n-max. = 50 Hz n-min 20 Hz n-max. = 45 Hz n-min OFF n-max. = 50 Hz = 5 Hz = 6 Hz Analog In 1 0...10 V 0...20 mA...
  • Page 27: Setting In Operation 1.02

    Operating Instructions Icontrol – model series FXDM Programming Step 4 value Factory setting: - - - - Setting range: Step 3 value - 50.0 Hz ** (or Step 5 value) Step 4 value Step 5 value Factory setting: - - - - Setting range: Step 4 value - 50.0 Hz ** Step 5 value * Minimal setting range depending on setting “Shutdown Freq.”...
  • Page 28: Temperature Control 2.01

    Operating Instructions Icontrol – model series FXDM Programming “Base setup”) Setting step (at Number steps: 1 - 5 Setting range: 0 - programmed number steps Factory setting: 0 Setting Step When setting a “min. speed” > OFF the output is not switched off in step “0”! Switching over to the protected “Info”...
  • Page 29: Settings For Operation Modes 2.01

    Operating Instructions Icontrol – model series FXDM Programming E2 Function • Funktion = External Setpoint via external signal (0 - 10 V) instead of “Setpoint 1” E2 Function “E1 Analog In” “TF” – For sensor type -27...+75.0 °C. : 0 - 10 V –...
  • Page 30: Functional Diagrams Temperature Control

    Operating Instructions Icontrol – model series FXDM Programming Min. Speed (basic speed only when needed) → “Shutdown Freq.” ( Motor Setup) - “Max. Speed”. Setting range: Factory setting: Min. Speed Max. Speed (speed limitation only when needed) Setting range: “Max. Frequency” ( Motor Setup) - “Min.
  • Page 31: Additional For Mode 2.03 : Signal Output 0 - 10 V

    Operating Instructions Icontrol – model series FXDM Programming Example 2: Temperature control in “Heating function” (Idealized principle diagram) 100 % Min. 0 % Max. = 100 % Max. 50 % Min. Min. 35 % Max. = 85 % 09.05.2007 20 °C 10 K 10 °C v_tempcontrol_heat_nmotor.vsd...
  • Page 32: For Mode 2.03 : Relay Output For Heating Or Cooling

    Operating Instructions Icontrol – model series FXDM Programming Example for signal out 0 - 10 V (IO Setup: “A function” = 10 V 100 % Min. 0 % Max. = 100 % Max. Analog Out Min. 35 % Max. = 85 % 50 % Min.
  • Page 33: Relay Output For Temperature Monitoring

    Operating Instructions Icontrol – model series FXDM Programming Temperature variation with reprogramming to for “K2” in IO Setup, e.g., for activation of the Cooling Example: Setpoint 15.0 °C, Offset +5.0 K, Hysteresis 2.0 K If the ambient temperature is higher than the set operat- OFF = 20°C - 2 K = 18 °C ON = 15°C + 5 K = 20 °C ing point, the cooling remains switched on.
  • Page 34: Setting For Operation Modes

    Operating Instructions Icontrol – model series FXDM Programming E1 Analog In For all Modes in Group 3 ( 3.01 3.02 3.03 , ...) “E1 Analog In” factory setting to “MBG-30I”. E1 Analog In (measuring range 0...30 bar) proportional output 4 - 20 mA Selection sensor: MBG-30I, MBG-50I, MBG-7I, DSF2-25 Alternative selection signal: 0 - 10 V, 4 - 20 mA, ( jumper for input signal) accordingly...
  • Page 35 Operating Instructions Icontrol – model series FXDM Programming Setpoint1 3.01 3.03 Setting range: in measuring range of sensor, factory setting: 12.0 bar 3.02 3.04 Setting range: dependent on the selected refrigerant, factory setting: Setpoint1 35.0°C Setpoint1 Setpoint2 Setting “Setpoint 2” e.g. reduced value for night operation. Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out: Setpoint2 Display:...
  • Page 36: Functional Diagrams Pressure Control Condensers

    Operating Instructions Icontrol – model series FXDM Programming 9.3.3 Functional diagrams pressure control condensers Functional diagram for Mode 3.01 3.03 (Idealized principle diagram) 100 % Min. 0 % Max. = 100 % 50 % Min. 17 bar 5 bar 12 bar 09.05.2007 v_diagramm_301_303_bar.vsd nM Motor speed...
  • Page 37: Pressure Control Airconditioning 4.01

    Operating Instructions Icontrol – model series FXDM Programming Pressure control airconditioning 4.01 4.03 4.01 4.03 9.4.1 Base setup Base setup Base setup Mode Mode selection e.g. 4.01 Mode E1 Analog In , ..) “E1 Analog In” factory setting In all group 2 operating modes 4 ( 4.01 4.02 4.03...
  • Page 38: Setting For Operation Modes 4.01

    Operating Instructions Icontrol – model series FXDM Programming 4.01 4.03 9.4.2 Setting for operation modes • 4.01 pressure control, setpoint in Pa • 4.02 4.03 Pressure control for ventilation systems setpoint depending on outdoor temper- ature Setting Setting Setpoint1 Setting range: in measuring range of sensor Factory setting: 100 Pa Setpoint1 Setpoint2...
  • Page 39: Volume Control

    Operating Instructions Icontrol – model series FXDM Programming Additional menu item for mode 4.02 4.03 with outside-temperature dependent target- setpoint. Outside-temperature dependent target-setpoint An outside temperature compensation can be activated (sensor connection “E2” = “Analog In 2”) when being operated as a pressure regula- Sollwert 1 [Pa] tion device.
  • Page 40: Setting For Operation Modes 5.01

    Operating Instructions Icontrol – model series FXDM Programming E1 Offset Sensor calibration with calibrated comparison device E1 Offset E2 Function (only for special applications) • External setpoint = Function by external signal (0 - 10 V) instead of “Setpoint 1” .
  • Page 41: Air Velocity Control 6.01

    Operating Instructions Icontrol – model series FXDM Programming Additional menu item for mode 5.02 with outside-temperature dependent target-setpoint Outside-temperature dependent target-setpoint An outside temperature compensation can be activated (sensor connection “E2” to “Analog In 2”) when being operated as a air volume regu- Sollwert 1 lation device.
  • Page 42: Settings For Operation Modes 6.01

    Operating Instructions Icontrol – model series FXDM Programming E2 Function (only for special applications) • External setpoint = Function by external signal (0 - 10 V) instead of “Setpoint 1” . 0 - 10 V 0 - 100 % sensor measuring range. E2 Function •...
  • Page 43: Menu Group Start

    Operating Instructions Icontrol – model series FXDM Programming Menu group Start Start Start Motor (Menu dependent on device type available) In this menu point the modulation for the motor can be switched on and off (ON / OFF). Factory setting to , this prevents the system from inadvertently starting up before configuration is complete.
  • Page 44: Menu Group Info

    Operating Instructions Icontrol – model series FXDM Programming Menu group Info Menu group Info Info Info for mode speed controller 1.01 Inverter output frequency. Frequency Display of motor current (Metering precision approx. +/-10%) Motor current Display of the currently active default signal. The percentage corresponds to the internal actuation of the power component under consideration of the settings “Min.
  • Page 45: Controller Setup

    Operating Instructions Icontrol – model series FXDM Programming Controller Setup 9.9.1 PIN protection activate, PIN 0010 The adjustments for the installation in the service level can be protected against unintentional modifications. To do this, activate the “PIN protection” = “ON”. In order to simplify the initial start-up operation, the service level in the factory setting is PIN Protection free = “OFF”...
  • Page 46: Limit

    Operating Instructions Icontrol – model series FXDM Programming 9.9.5 Limit After allocation of a digital input ( IO Setup) an adjustable limitation of the modulation can be activated via a digital input (“D1”, “D2”, ..). As long as no allocation has been carried out “IO Setup”. Display: - - - - Limit “Limit value”...
  • Page 47: Group Control

    Operating Instructions Icontrol – model series FXDM Programming 9.9.7 Group control 9.9.7.1 Control group 2 via 0 - 10 V output Group 2 ON value Switch-on value for Group2 Setting range: 0 - 100 % Group 2 ON value Factory setting: 50 % * OFF Value Group2 Switch-off value for group2 Setting range: 0 - 100 %...
  • Page 48: Control Group 2/3/4 Via Relais

    Operating Instructions Icontrol – model series FXDM Programming 9.9.7.2 Control group 2/3/4 via relais Group 2 ON value Switch-on value for Group2 Setting range: 0 - 100 % Group 2 ON value Factory setting: 50 % * OFF Value Group2 Switch-off value for group2 Setting range: 0 - 100 % OFF Value Group2...
  • Page 49: Reverse Action Of The Control Function

    Operating Instructions Icontrol – model series FXDM Programming Example: Activation of 3 groups via relays G3 ON = 70 % G2 ON = 50 % G4 ON = 85 % Controller Fout Standard Master 0 ...100 % Digital Out Z-Modul-B Analog Signal OFF = 0 %...
  • Page 50: Controller Configuration

    Operating Instructions Icontrol – model series FXDM Programming 9.9.9 Controller configuration The “controller configuration” is automatically carried out during selection of the application related mode of operation (Base setup). The factory presets in accordance with the mode of operation are based on many years of experience, which is suitable for many applications.
  • Page 51: Io Setup

    Operating Instructions Icontrol – model series FXDM Programming 9.10 IO Setup “A” 9.10.1 Analog-Output The analog outputs 0 - 10 V can be allocated with various functions. Terminals “A” - “GND” = Analog Out (I 10 mA) A Function With the attitudes “A min” and “A max” the characteristic of the output voltage can be adapted.
  • Page 52: Digital Inputs "D1" / "D2

    Operating Instructions Icontrol – model series FXDM Programming “D1” “D2” 9.10.2 Digital inputs 9.10.2.1 Menu overview The digital inputs Digital In 1 (D1) and Digital In 2 (D2) can be allocated with various functions. Activation via floating contacts (a low voltage of approx. 24 V DC is connected). D1 Function Inverting “D1”...
  • Page 53: External Fault Function | 2D

    Operating Instructions Icontrol – model series FXDM Programming STOP Display for switch OFF Digital IN 1 Digital IN 1 • “ON” Controller for closed contact (factory setting). • “OFF” Controller with opened con- tact When inverting in reverse i.e. equipment 10.05.2007 “OFF”...
  • Page 54: Set 1/2 Or Setpoint 1/2, Function

    Operating Instructions Icontrol – model series FXDM Programming Si 1 Si 2 Controller Si 1 n = 0- 100 % Si 2 D1 D1 26.05.2010 v_4d_umschaltung_e1_e2.vsd Si 1 Signal 1 Si 2 Signal 2 ) Base setup for “E2 Analog In”: For mode speed controller ( 1.01 necessary.
  • Page 55: Intern / Extern Function | 6D

    Operating Instructions Icontrol – model series FXDM Programming 9.10.2.7 Intern / Extern Function ). “Set extern1” Switch over between Set Intern and Set Extern (for mode speed controller 1.01 under settings must be programmed to “OFF”. Contact e.g. at ditgital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” - “24 V”).
  • Page 56: Reset, Function | 10D

    Operating Instructions Icontrol – model series FXDM Programming The factory presets for the “Control function” are dependent on the selected mode of operation ( Controller Setup - reverse operation of the control function). When switching over via a digital input, the device works with the opposite function as set there. Settings in Controller Setup Val>Set=n+ 9.10.2.10...
  • Page 57: Direction Of Rotation, Function | 13D

    Operating Instructions Icontrol – model series FXDM Programming The motor heating can be activated over a digi- tal input. E.g. over a freeze protection thermostats at digital input “Digital In 1” (depending on device type at terminals “D1” - “D1”or “D1” - “24 V”). - - - - - Controller Motor heating active at closed contact, if no...
  • Page 58: Configuration Of Analog Inputs "E1"And "E2

    Operating Instructions Icontrol – model series FXDM Programming “E1” “E2” 9.10.3 Configuration of analog inputs 9.10.3.1 Signal adaption E1 and E2 If required, an adaptation of the specification signal / speed characteristic curve is possible Information These settings are mostly practical for the operating mode with rotational speed specification over an external signal.
  • Page 59: Inverting Analog Inputs "E1" / "E2

    Operating Instructions Icontrol – model series FXDM Programming “1.01” Example for Mode with speed setting signal 0 - 10 V Modus 1 Modus 1 Example: “E1 min.” = 20 % [Hz] The controller begins only at approx. 20% higher signal with minimal modulation. E1 min.
  • Page 60: Function And Inverting For Relay Outputs "K1" And "K2

    Operating Instructions Icontrol – model series FXDM Programming Example: mode speed controller, setting by external signal 100 % Min. 0 % Max. = 100 % Min. 35 % Max. = 85 % 50 % Min. 0 – 10 V 10 – 0 V 0 –...
  • Page 61: Programming Add-On Module Type Z-Modul-B

    Operating Instructions Icontrol – model series FXDM Programming Group control (Group 2) Switching on fans depending on modulation 12K * Group control (Group 3) Switching on fans depending on modulation 13K * Group control (Group 4) Switching on fans depending on modulation For modes as controller higher 2.01 Setpoint Offset...
  • Page 62: Networking Via Modbus

    Operating Instructions Icontrol – model series FXDM Programming • 2 x relay outputs (“K3” and “K4”) Function programmable, e.g., for: Status signals, alarm indications, external malfunctions at the digital input, level-control threshold, input signal thresh- old, offset threshold (deviation between current and target value), group control. Parameter Factory setting User Setting...
  • Page 63: Limits

    Operating Instructions Icontrol – model series FXDM Programming 9.11 Limits 9.11.1 Limit indication depending on modulation Following functions can be allocated to the limit indication without function Indication with the centralized fault of a programmed relay (IO allocation Level. Function Function Warning symbol in display, “AL”...
  • Page 64: Limit Indication Depending On Setting Or Sensor Signal

    Operating Instructions Icontrol – model series FXDM Programming 9.11.2 Limit indication depending on setting or sensor signal Following functions can be allocated to the limit indication without function Indication with the centralized fault of a programmed relay (IO allocation Lmt E1 Function Function Warning symbol in display, “AL”...
  • Page 65: Limit Indication Depending On (Offset) To Setpoint

    Operating Instructions Icontrol – model series FXDM Programming 9.11.3 Limit indication depending on (offset) to Setpoint In operating modes as a controller (via 2.01 ), two limit indicators can be carried out based on the set target value (Setpoint) and measured actual value (on E1). Following functions can be allocated to the limit indication without function Indication with the centralized fault of a programmed relay (IO allocation...
  • Page 66: Motor Setup

    Operating Instructions Icontrol – model series FXDM Programming 9.12 Motor Setup Menu group Motor Setup Motor Setup 9.12.1 Setting motor rated current MotorRatedCurr. When commissioning, you must set the motor to the rated current stated on the rating plate. MotorRatedCurr. Setting range: 0.0...device rated current / A Factory setting: device rated current 9.12.2...
  • Page 67: Setting For Rampup Time And Rampdown Time

    Operating Instructions Icontrol – model series FXDM Programming edge 100 % = 10 % start = 0 % [Hz] start Analog In 1 0...10 V 0...20 mA 90 100 0...100 % PWM 26.07.2012 v_u_f_dia_icontr_d.vsd Uout Output voltage Fout: Output frequency Analog In Speed setting signal (0 - 10 V, 0...20 mA, 0...100 % PWM) Ustart Start-up voltage Foff Shutdown Freq.
  • Page 68: Setting Switching Frequency

    Operating Instructions Icontrol – model series FXDM Programming 0 .. 100 % 09.05.2007 v_hochlaufzeit_ruecklaufzeit.vsd 1 external Signal 2 Setting 3 Rampup time 4 Rampdown time 9.12.5 Setting switching Frequency Switching Freq. Setting range FXDM2.6 - 25: 8.0 / 10.0 / 16.0 kHz Setting range FXDM32 - 62: 6.0 / 8.0 / 10.0 / 16.0 kHz Switching Freq.
  • Page 69: Setting Current Limit

    Operating Instructions Icontrol – model series FXDM Programming 9.12.7 Setting Current limit As an additional safety function the device has a current limit, this can be adapted if necessary. The setting refers to the motor rated current of the device (100 % = setting: MotorRa- Current limit tedCurr.).
  • Page 70: Setting Boost Value

    Operating Instructions Icontrol – model series FXDM Programming 9.12.9 Setting Boost value The boost function is an automatic voltage increase when the control system is under dynamic requirements. When using the square characteristic curve, the output voltage is increased dispropor- tionately to the frequency during a 20% increase of the modulation.
  • Page 71: Setting Overmodulation

    Operating Instructions Icontrol – model series FXDM Programming 9.12.11 Setting Overmodulation In the as-delivered state the maximum output voltage for operation without overmodulation is approx. 95 % of the applied mains voltage. In operation with overmodulation the maximum output voltage can reach about the level of the applied mains voltage.
  • Page 72: Suppression Of Speeds

    Operating Instructions Icontrol – model series FXDM Programming 9.12.13 Suppression of speeds Suppression of up to three speed ranges. Under certain circumstances, it is possible to prevent disturbing noises that can arise at certain speeds due to resonances. Example for suppression of 2 ranges (Idealized principle diagram) 100 % 50 % 35 % max...
  • Page 73: 10 Menu Tables

    Operating Instructions Icontrol – model series FXDM Menu tables 10 Menu tables 10.1 Menues of operating modes Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** Start Motor PIN input...
  • Page 74 Operating Instructions Icontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** - - - - - Setpoint2 - - - - - - - - - - - - - - - - - - - -...
  • Page 75 Operating Instructions Icontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** 1.02 = - - Step 5 value - - - 3.02 = 3.04 =...
  • Page 76 Operating Instructions Icontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** Group 4 ON value - - - - - - - - - - - - - - - - - - - -...
  • Page 77 Operating Instructions Icontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** - - - - - E2 min. - - - - - - - - - - - - - - -...
  • Page 78 Operating Instructions Icontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** Offset 1 - - - - - - - - - - - - - - - - - - - -...
  • Page 79: Possible Allocation Of The Ios, Pins

    Operating Instructions Icontrol – model series FXDM Menu tables Mode User Setting 2.01 4.01 1.01 3.01 3.03 5.01 2.03 2.02 2.05 4.02 6.01 1.02 3.02 3.04 5.02 2.04 4.03 Parameter Factory setting *** E2-Voltage 0.00 V 0.00 V 0.00 V 0.00 V 0.00 V 0.00 V...
  • Page 80 Operating Instructions Icontrol – model series FXDM Menu tables Function Description function D1..D5 Motorheating ON / OFF (not Acontrol) Reverse direction of rotation “right-hand” / “left-hand” (only for frequency inverter with 3 ~ output) “Freeze function” = maintain momentary modulation value Analog inputs E2 / E3 Function Description Function E2...
  • Page 81: 11 Diagnostics Menu

    Operating Instructions Icontrol – model series FXDM Diagnostics menu Cooling function Switch ON point: temperature = Setpoint +/- Offset Switch OFF point: Temperature around hysteresis below switch ON point * Function depending on the version of the software available Limits GW E1, GW E2 Function Description function GW E1, GW E2 without function...
  • Page 82 Operating Instructions Icontrol – model series FXDM Diagnostics menu E1-Current E1-Voltage E2-KTY Signal height at analog input E2 (Analog In 2) E2-Current E2-Voltage Signal height at analog input E3 (Analog In 3*) Status digital input 1 (Digital In 1) OFF = terminals D1 - D1 bridged ↔ ON = terminals D1 - D1 not bridged Status digital input 2 (Digital In 2) OFF = terminals D2 - D2 bridged ↔...
  • Page 83: Special Features For Measurements At The Innverter And Motor

    Operating Instructions Icontrol – model series FXDM Events / Fault signals * When operating together with the “Z-Modul-B” type add-on module, the diagnosis menu is automati- cally expanded to include the additional inputs and outputs (installation not possible in Icontrol flat). 11.1 Special features for measurements at the innverter and motor 11.1.1...
  • Page 84: Messages And Trouble Shooting

    Operating Instructions Icontrol – model series FXDM Events / Fault signals 12.2 Messages and trouble shooting A momentary pending alarm or error message is indicated by a blinking indicator and appears alternately with the standard display. Operating conditions are indicated by the internal status LED with flashing code. internal State LED 11.02.2009 v_flash_explain.VSD...
  • Page 85 Operating Instructions Icontrol – model series FXDM Events / Fault signals Display Code* LED Code Relais switches Possible cause Reaction of Controller Opera- internal Fault Adjustment tion Controller loaded the User Setup automatically (if Warning message, operation available). E.g. in case of with User Setup MC User Setup faulty parameter data.
  • Page 86 Operating Instructions Icontrol – model series FXDM Events / Fault signals Display Code* LED Code Relais switches Possible cause Reaction of Controller Opera- internal Fault Adjustment tion Inverter switches off motor. New start-up attempt after Short-circuit at motor con- about one minute (4x error then nection to earth (U, V, W) lock).
  • Page 87: 13 Function Extension And Version Of Software

    Operating Instructions Icontrol – model series FXDM Function extension and version of software Display Code* LED Code Relais switches Possible cause Reaction of Controller Opera- internal Fault Adjustment tion Actual value exceeds set- point selecta- Lmt Offset 1 Device continues working un- changed Actual value drops below Check setting and sensor...
  • Page 88: 14 Enclosure

    Operating Instructions Icontrol – model series FXDM Enclosure 14 Enclosure 14.1 Technical data The name plate data for the rated current* output refer to a maximum ambient temperature of 40 °C. For higher temperatures note following position for operation with higher ambient temperature. Rated cur- Rated cur- Recom-...
  • Page 89 Operating Instructions Icontrol – model series FXDM Enclosure Rated cur- Rated cur- Recom- max. line max. heat Noise ap- Weight Housing rent* rent mended fuse dissipation prox. protection motor out- Output (I funda- [kg] mental com- [dB] Type ponent @ (Part-No.) 50 Hz) [kW]...
  • Page 90: Versions Type-Lines Icontrol

    Operating Instructions Icontrol – model series FXDM Enclosure Please ask manufacturer for the individual harmonic oscillation levels of the current as a percentage of the fundamental oscillation of the rated current. FXDM2.6...25 and FXDM32E...62E Vibratory strength Broadband noise (simulated life-endurance test) in accordance with EN 61373, (for vertical installation, i.e.
  • Page 91 Operating Instructions Icontrol – model series FXDM Enclosure 8 kHz Maximal motor current for clock frequency depending on line voltage and ambient temperature Type 208 V (-15 %)...415 V (+6 %) over 415 V (+6 %)...480 V (+10 %) 40 °C 50 °C 55 °C 40 °C...
  • Page 92: Connection Diagram

    Operating Instructions Icontrol – model series FXDM Enclosure 14.2 Connection diagram Icontrol FXDM...A(E)(Q) Kontaktbelastung Contact rating Adressierung max. AC 250 V 2 A °C Addressing TB/TP Digital Analog 24 V DC Analog Analog Digital Normal In 1 Out 1 In 1 In 2 In 2 GND TB/...
  • Page 93: Dimensions [Mm]

    Operating Instructions Icontrol – model series FXDM Enclosure 14.3 Dimensions [mm] FXDM2.6A / FXDM2.6AQ FXDM4.2...17A (FXDM25A) / FXDM4.2...17AQ (FXDM25AQ) FXDM4.2...17A Q (FXDM25A Q): Position of switch for plan view without obligation L-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB 93/96...
  • Page 94 Operating Instructions Icontrol – model series FXDM Enclosure FXDM32...62A / FXDM32...62AQ (IP54) FXDM32...62AE (IP20) L-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB 94/96...
  • Page 95: Index

    Operating Instructions Icontrol – model series FXDM 14.4 Index Maximum frequency MBG-30I, MBG-50I address Minimum space requirement Average calculation Minimum speed cut off MODBUS Mode Base setup motor leads are connected bypass switching motor noises Motor protection clock frequency control cable Outdoor installation Current measurements output voltage...
  • Page 96: Manufacturer Reference

    Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau Telephone: +49 (0) 7940 16-0 Telefax: +49 (0) 7940 16-504 info@ziehl-abegg.de...