Electromagnetic Compatibility (Emc) - ABB CP 600 Series Operating Instructions Manual

Hide thumbs Also See for CP 600 Series:
Table of Contents

Advertisement

Electromagnetic Compatibility (EMC)

Test executed on the 230 V AC side of the Power Supply (EN 61000-4-11).
Parameter
Radiated disturbance test
Electrostatic discharge im-
munity test
Radiated, radio-frequency,
electromagnetic field immuni-
ty test
Burst immunity test
Surge immunity test
Immunity to conducted dis-
turbances inducted by radio-
frequency field
Voltage dips, short interrup-
tions and voltage variations
immunity test
Value
Class A
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
80 MHz ... 1 GHz, 10 V/m
1.4 GHz ... 2 GHz, 3 V/m
2 GHz ... 2.7 GHz, 1 V/m
± 2 kV DC power port
± 1 kV signal line
± 0.5 kV DC power port (line to earth)
± 0.5 kV DC power port (line to line)
± 1 kV signal line (line to earth)
0.15 ... 80 MHz, 10 V
Port: AC mains. Level:
100 % / duration: 1 cycle and 250 cycles (50 Hz);
40 % / duration: 10 cycles (50 Hz);
70 % / duration: 25 cycles (50 Hz);
Phase: 0°-180°
9
CP620, CP630, CP635, CP651, CP661, CP665, CP676
According to
EN 55011
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6