6. Enclosure Specifications

The Thermocouple Card is mounted in the TLX enclosure.
Body Type
Hazloc Rating
Mounting
Operating Temperature
Storage Temperature
Probe
Measurement Temperature Range
Optional: Temperature Probe Operating Range
Optional: Temperature Probe Union Operating Range

7. Instructions for Use

The Thermocouple card is designed to be used with a certified BMS controller as part of the PF3100 platform.
Operation
Operating controls and their uses are described under the Terminal Descriptions section.
8. Preventative Maintenance & Inspection
In order to ensure that the Thermocouple card works correctly and efficiently, the following maintenance and
inspection procedures should be followed:
➢ Ensure that all wires are connected correctly.
➢ Check for corrosion and ensure that no wires are frayed or worn, and all insulation is intact.
➢ Confirm no moisture or condensation is apparent on the board or in the enclosure.
➢ Ensure that the board does not show any sign of mechanical damage (e.g. – damage from an impact such as
dropping an item).
➢ Ensure that the board does not show any sign of electrical damage (components should not be burnt or
damaged in any way).
➢ Confirm that the temperature of the board is within ambient temperature operating limits.
➢ Check that the enclosure is secured and that the device is not subject to excessive vibration.
➢ Routine inspections of all equipment should be performed. If any abnormality is found, corrective actions should
be taken. If the abnormality cannot be corrected, contact PROFIRE.
➢ A qualified technician should perform any tests necessary to confirm that the equipment is still in a safe
condition.
Ensure power LED is lit (blue)
Ensure link LED is lit (green)
PROFIRE
1.855.776.3473
solutions@profireenergy.com
Specifications
PF3100 Thermocouple Card Product Manual
TLX Enclosure
Standard 1/2" NPT Head Connection
Class I, Div 1, Grp BCD, T4
1/2" NPT Thermowell
-40°C (-40°F) to 60°C (140°F)
-40°C (-40°F) to 60°C (140°F)
11.5" Probe Dual Element Type K Thermocouple, pre-
wired to TC1A and TC1B inputs
-200°C (392°F) to +1350°C (2462°F)
0°C (32°F) to +925°C (1697°F)
-40°C (-40°F) to +250°C (482°F)