Download Print this page

Emerson Rosemount 644 Quick Start Manual page 30

Temperature transmitter with 4–20 ma hart protocol
Hide thumbs Also See for Rosemount 644:

Advertisement

Quick Start Guide
Standards: EN 60079-0: 2012+A11: 2013, EN 60079-31: 2014, EN
Markings:
See
Table 4-1
Special Conditions for Safe Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become
a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4
joules.
4. Flameproof joints are not intended for repair.
5. A suitable certified Ex d or Ex tb enclosure is required to be connected
to temperature probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external
surface temperature on the equipment and the neck of DIN Style
Sensor probe does not exceed 130 °C.
7. Non-Standard Paint options may cause risk from electrostatic
discharge. Avoid installations that cause electrostatic build-up on
painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information
4.7
International
4.7.1
E7 IECEx Flameproof
Certificate: IECEx FMG 12.0022X
Standards: IEC 60079-0: 2011, IEC 60079-1: 2014
Markings:
See
Table 4-1
Special Conditions for Safe Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become
a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4
joules.
30
60529:1991 +A1:2000
II 2 D Ex tb IIIC T130 °C Db, (–40 °C ≤ T
for process temperatures.
Ex db IIC T6...T1 Gb, T6(–50 °C ≤ T
T
≤ +60 °C)
a
for process temperatures.
≤ +70 °C); IP66
a
≤ +40 °C), T5...T1(–50 °C ≤
a
Emerson.com/Rosemount
May 2019

Advertisement