4. To end the loop test, select End and Enter.
2.5.2
Perform a loop test using Device Manager
Procedure
1. Right click on the device and select Service Tools.
2. In the left navigation pane select Simulate.
3. On the Simulate tab in the Analog Output Verification group box,
select the Perform Loop Test button.
4. Follow the guided instructions and select Apply when complete.
2.5.3
Perform a loop test using the LOI
Reference the figure below to find the path to the Loop Test in the LOI
menu.
Figure 2-9: Configuring the Tag with LOI