HMI5000L Series Installation Guide Introduction Thank you for purchasing a Maple Systems HMI5000L Series graphic industrial operator interface terminal. This booklet describes the steps necessary for installing the following models: • HMI5043L • HMI5070LB • HMI5100L • HMI5043LB • HMI5070NL •...
USB Stick Clamp and Spare Fuse Kit (Not on all models) Warranty A copy of the Warranty and Limitation of Liability is contained in the product box. It can also be found on the Maple Systems website. 1010-1018 Rev 10 www.maplesystems.com...
Page 3
Web: www.maplesystems.com Installation of HMIs Information furnished by Maple Systems is believed to be accurate and reliable. However, no responsibility is assumed by Maple Systems for the use of this information, or for any infringements of patents or other rights of third parties which may result from its use.
HMI5000L Installation Guide Environmental Considerations The HMI is designed to operate in temperatures from 0° to 50°C (32° to 122°F). It is intended for indoor installations and may not be suitable for use in certain outdoor applications. Avoid installing the HMI in environments with severe mechanical vibration or shocks.
HMI5000L Installation Guide Cable Routing and Noise Immunity Follow these guidelines when routing cables to the HMI: • Always route the HMI communication cable and the power cable away from any AC voltage or rapidly switching DC control lines. • Never bundle the HMI cables together with 120VAC power wires or with relay wiring.
For a more in-depth overview of ground wiring techniques, refer to Technical Note #1027, “OIT Ground Wiring and Electrical Noise Reduction” in the Technical Notes section of the Maple Systems website. Installation It is necessary to follow all installation procedures described in this chapter for electrical noise immunity and CE compliance.
Page 8
HMI. The power cable for the HMI should be 18AWG, 2-conductor wire with a shield drain wire and protective shield (foil/braid). Cable (P/N 6030-0009) may be purchased by the foot from Maple Systems for constructing power cables. Always run the DC ground wire directly back to the signal return of the power supply.
Cutout dimensions for each particular HMI model are available for print and download from the Support Center-Dimensional Drawings section of the Maple Systems website. The area of the panel or mounting surface where the gasket comes into contact must be flat and free of scratches, pits, and other features that prevent the gasket from sealing properly.
If there is a difference in ground potential (voltage), making a connection via a USB cable can complete a ground loop that may damage the HMI and PC. The Maple Systems USB Configuration Cable (P/N 7431-0115) is recommended for connecting the HMI to the PC.
Page 11
HMI5000L Installation Guide Ethernet If using a switch or router between the PC and the HMI, use a straight- through or crossover cable as required by the switch or router. In order to download a project to the HMI over Ethernet, the HMI must be assigned a unique IP address that is on the same subnet as the development PC.
Boot Loader mode: This mode is used when replacing or reinstalling the operating system and is intended for use by qualified repair personnel only. Improper use by setting to ON may damage the HMI. Contact Maple Systems for more information. 1010-1018 Rev 10 www.maplesystems.com...
Page 13
EasyAccess 2.0 makes remote monitoring of your HMI easy. For more information on EasyAccess 2.0, please visit the EasyAccess 2.0 section of the Maple Systems website. Fusing Requirements If the display does not come on within two seconds of power up, remove power.
HMI5000L Installation Guide Dual Ethernet Port Information and Network Configuration The HMI5043DL, HMI5070DL, and HMI5097DXL feature two Ethernet ports. In order to utilize both ports, they need to be configured properly. Default settings: Port LAN1 is configured as a DHCP Client (Dynamic IP). Port LAN2 is configured as follows: •...
Page 17
HMI5000L Installation Guide Wi-Fi Connectivity and Network Configuration (HMI5103L) The HMI5103L features Wi-Fi connectivity in addition to the standard RJ45 Ethernet port. Supported Wi-Fi modes are IEEE 802.11 b/g/n, with WPA-PSK/WPA2-PSK encryption. Wi-Fi is off by default. To enable and configure Wi-Fi: 1.
Page 18
Note: When using the Wi-Fi simultaneously with the wired Ethernet port, ensure that the connections are on different subnets. Detailed instructions of the HMI5103L Wi-Fi capabilities are provided in Tech Note 5121, available from the Support Center of the Maple Systems website. 1010-1018 Rev 10...