Page 2
Declaration of Conformity Edwards Limited, Crawley Business Quarter, Manor Royal, Crawley, West Sussex, RH10 9LW, UK declare under our sole responsibility, as manufacturer and person within the EU authorised to assemble the technical file, that the product(s) Turbomolecular Pump Controllers...
Page 3
P200-10-033 Issue A Material Declaration In accordance with the requirements of the Chinese regulatory requirement on the Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products Order No. 32 (also known as ‘China RoHS2’) and SJ/T 11364 Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products: Product Product Label...
Introduction Scope and definitions This manual provides installation, operation and maintenance instructions for the Edwards EXC120, EXC120E, EXC300 and EXC300M Turbomolecular Pump Controllers (abbreviated to Controller in the remainder of this manual). You must use the Controller as specified in this manual.
Controller (see Section 1.9.2). You can use the EXC120, EXC300 and EXC300M Controllers as stand-alone controllers. Alternatively, you can connect the Controller to your own equipment; you can then use either the Controller or your own equipment to control the system.
In addition to the controls and indicators on the front panel, the EXC120, EXC300 and EXC300M Controllers have an electrical supply isolator on the rear panel (see Figures to 5). The controls and indicators on the front panel of the EXC120, EXC300 and EXC300M Controllers are shown in Figures and are described below. Start/Stop Use this latching button to alternately Start or Stop the EXT pump.
Bakeout band control (EXC120/300/300M only) The EXC120, 300 and 300M Controllers can be used to operate a bakeout band. The Controller will switch on the electrical supply to the bakeout band when the Heater switch on the front panel is switched on and the EXT pump is at Normal speed (refer to Sections and 1.7.4).
Backing pump control (EXC120/300/300M only) The EXC120, EXC300 and EXC300M Controllers can be used to control the operation of a backing pump through a backing pump relay. The operation of this relay depends on how you have configured the Controller to operate the vent-valve: refer to Sections and 3.13.
Start/Stop Use the Start/Stop input to Start and Stop the EXT pump. Note that on the EXC120, EXC300 and EXC300M Controllers, the signal is wired in series with the Start/Stop button on the front panel, so you must close the Start/Stop input and press the Start/Stop button on the front panel to Start the pump.
When the Controller trips into Fail condition: the electrical supply to the EXT pump-motor is switched off the TMP Fail status output signal on the logic interface opens and (on the EXC120, EXC300 and EXC300M Controllers) the Fail LED on the front panel goes on.
The Controller can be used on a bench-top or can be fitted in a rack or cabinet. You can operate the EXC120, EXC300 and EXC300M Controllers in a horizontal position or in a vertical position with the front panel at the top. You can operate the EXC120E Controller in a horizontal position or in a vertical position with the side vents at the top.
15 and 16 linked together on the mating connector. †† The EXC120/E Controller is supplied with pins 8 and 9 linked together, pins 12 and 13 linked together and pins 14 and 15 linked together on the mating connector.
D396-14-880 Issue J Figure 8 - Schematic diagram of EXC120 & EXC120E Controller electrical connections A. Vacuum and control system L. Live electrical supply B. EXC Controller N. Neutral electrical supply E. Earth (ground) electrical supply 1. External electrical supply 14.
Connect the brown wire to the live electrical supply. Connect the blue wire to the neutral electrical supply. 2. On EXC120, EXC300 and EXC300M Controllers, ensure the electrical supply isolator on the rear panel is in the off position. 3. Fit the connector on the other end of the electrical supply cable to the electrical supply connector on the rear of the Controller (see Figures to 5).
Interlock, you must remove the link fitted to the TMP Interlock control input on the logic interface; that is: On EXC120 and EXC120E Controllers, remove the link between pins 12 and 13. On EXC300 and EXC300M Controllers, remove the link between pins 13 and 14.
Figures and 9). On the EXC120, EXC300 and EXC300M Controllers, the LED on the Standby button will go on when the Standby mode is selected (either by the button or the logic interface). If you select Standby when the pump is operating, the speed of the pump will be reduced to the Standby speed. If you select Standby before you switch the pump on, the pump will run up to Standby speed, not up to full speed.
Use the following procedure to shut down your system. This procedure assumes that you will manually operate the vent-valve and the backing pump, however you can configure all EXC Controllers to automatically operate the vent- valve and you can configure the EXC120, EXC300 and EXC300M Controllers to automatically operate the backing pump (refer to Section 3.13).
Ensure that people cannot be injured by the rotating rotor blades of the EXT pump. The EXC120, EXC120E and EXC300 Controllers will automatically switch off the electrical supply to the EXT pump if the Controller trips into Fail condition (see Section 1.9), though the EXC300M Controller will continue to provide an...
ACX air-cooler An ACX air-cooler can be fitted to the EXT pump and can be operated automatically from the EXC120, EXC300 and EXC300M Controllers. However, please refer to Section 3 of the instruction manual for the EXT pump to check the suitability of air cooling in a particular application.
Figures and 15. The Active Gauge connector (which is specific to the EXC Controller) is shown in Figure Figure 14 - EXC120/120E/300 Controller to EXT pump connections A. EXT pump 1. DC motor B. EXT connector on cable 2. Speed set resistor C.
Need help?
Do you have a question about the EXC120 and is the answer not in the manual?
Questions and answers