• 12.0 Parameter Mode:
The following tables give the detailed descriptions. Please note that 20sec of
inactivity will take the unit back in normal mode and all the changes done
shall be cancelled.
• 12.1
System Parameter
Parameter
Name on
LCD & Icon
Enter
Systems setting are password
Password
protected. Password is a three digit
number
System
ECON provides complete flexibility in
Config
system designing; it is possible to
select auto and manual operation for
any combination of mains and DG
A/M
phases. E.g. mains 3 phase and DG
single phase or vice versa, or three
phase mains and DG, or single
phase mains and DG.
Solenoid
Pull To Start
Type
In this mode fuel solenoid contact
changes from Open to Close at the
time of cranking and remains close
till the genset is running. For stopping
the generator this contact opens.
Pull To Stop
In this mode fuel solenoid contact
remains open at the time of cranking
and till the genset is running. For
stopping the generator this contact
closes for a user programmed time.
LLOP
Select the installed sensor for LLOP
Sensor
Type
Operating Instructions
Explanation of Parameter
Factory
Setting Range
Setting
123
M:3P/G:1P AMF M:3P/G:1P
AMF M:3P/G:3P
AMF M:1P/G:1P
MANUAL1P
MANUAL 3P
AUTO STOP 1P
AUTO STOP 3P
Pull to
Pull to Stop
Stop
Pull to Start
Type A
Type A
Type B,
M&M,
MNEPL,
VE, TMTL,
HUAFANG,
TATA,
GC(VDO), GC
(MURPHY),
Disabled *
0-999
Page - 11