Design And Device Parts; Dimensions - Siemens OpenAir G..B181.1E/KN Series Technical Basics

Vav compact controller knx/pl-link
Table of Contents

Advertisement

Main device parts
Gear train
disengagement
12 / 44
Siemens
Building Technologies
2.2

Design and device parts

The VAV compact controllers consist of a differential pressure sensor, actuator and
digitally configurable control electronics. They are intended for mounting on
damper shafts of a minimum length of 30 mm. They consist of base and 2-sectional
housing.
Components contained in the base:
∂ Steel base plate with damper drive shaft fixing for different drive shaft
diameters / cross-sectional areas (cf. section 2.3) and angular rotation limiter,
∂ maintenance-free, low-noise gear train,
∂ magnetic hysteresis clutch with practically contact-free force transmission; this
means that the actuator is locking- and overload-proof, also in continuous
operation.
Components contained in the housing (Note: the housing cover must not be
removed):
∂ Controller electronics,
∂ differential pressure sensor,
∂ synchronous motor for the damper actuator.
1
2
3
4
Manual control of the air dampers is possible by gear train disengagement (8)
when the VAV compact controller is disconnected from the power supply.
2.3

Dimensions

43
87
137
158
min. 100
Measures in mm
VAV compact controller KNX/PL-Link G..B181.1E/KN
1
Shaft attachment screw
10
2
LED
3
Push button
4
Configuration and maintenance interface (below cover)
5
Connection nozzle for measuring differential pressure in
the VAV box
9
6
Connection nozzle for measuring differential pressure in
the VAV box ("+": Side with higher pressure)
7
Two connecting cables (power and communications),
2-core each
8
8
Disengagement of gear train
9
Rotation angle display
7
10 Rotation angle check screw
6
5
8
Ø 3...8
min. 80
X
20
2
3547M01
X =
8 - 16 mm
12.8 mm
15 mm
CE1P3547en
2017-03-23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Openair gdb181.1e/knOpenair glb181.1e/kn

Table of Contents