Application planning
4.3 Power balance calculation
Power balance calculation during planning with STEP 7
Compliance with the power balance is reviewed during planning by STEP 7.
Proceed as follows to evaluate the power balance calculation:
1. Configure the configuration of the S7-1500 with all the required modules.
2. In the network view, select the CPU or the system power supply.
3. Open the "Properties" tab in the inspector window.
4. Select the "System power supply" entry in the area navigation.
5. Check the "Power balance calculation" table, so see whether the power balance is
Figure 4-7
Power balance check by the CPU for overload
Compliance with a positive power balance is monitored by the CPU:
● At every POWER ON
● At every change of the installed hardware
Causes for overload
An overload can still occur despite a positive power balance during planning. The cause for
overload can be a hardware configuration that does not correspond to the planning in
STEP 7 (TIA Portal), for example:
● More I/O modules are inserted in the actual configuration than were planned
● A system power supply that is necessary for operation is not inserted
● A system power supply that is necessary for operation is not switched on (power cable
● A system power supply that is necessary for operation has no U connector inserted
36
positive. If the power balance is negative, the underpowered modules will be marked in
red.
Example of a power balance calculation with STEP 7
connector and on/off switch)
S7-1500 Automation System
System Manual, 01/2013, A5E03461182-01