V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

OPERATION

To function as intended, the V4062 must be connected to a
properly sized valve. Too large a valve will not properly control
the gas flow.
When the actuator is energized, it drives to the adjustable
low-fire position. Depending on the demand of the controller,
the valve remains at low-fire or moves to the high-fire position.
When the firing rate controller calls for no heat, the actuator
returns the valve to the low-fire position. When power to the
actuator is interrupted, the valve completely closes.
Fig. 4 shows the V4062 in a typical flame safeguard control
system.

SERVICE AND CHECKOUT

CAUTION
Equipment Damage Hazard.
Unskilled technicians can damage the equipment.
Only experienced, trained flame safeguard control
service technicians should service or replace this
control.
Service
The actuator is not field repairable, except for replacing the
auxiliary switch or valve-closed indication switch. See
Installation section for procedure. Do not disassemble the
valve actuator. If the actuator should fail to operate properly,
replace it.
Checkout
After the installation is complete, cycle the valve several times
with the manual fuel shutoff cock closed before testing the
system in actual operation.
V4062A1156 Fluid Power Gas Actuator
The V4062A1156 Fluid Power Gas Valve Actuator was
modified to provide modulation between high-and low-fire
positions when used with a Series 60 controller, such as the
W964 Aquatrol™ System and two auxiliary relays.
The V4062A1156 will not operate properly wired similarly to
other V4062 models. See Fig. 7 for suggested wiring
procedure.
Ratings:
Voltage: 120V, 60 Hz.
Nominal Opening Time: 26 seconds.
Closing Time: one second maximum.
Home and Building Control Home and Building Control
Honeywell
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN 55422
Scarborough, Ontario
M1V 4Z9
60-2099—9
G.R. Rev. 2-01
See Specifications section for further specifications.
INDOOR
SENSOR
1
1
R1
RELAY
CONTACT
C
AUX.
NC
SWITCH
NO
1
R1 – NORMALLY CLOSED RELAY CONTACT.
2
R2 – NORMALLY OPEN RELAY CONTACT.
Fig. 7. Suggested wiring diagram.
Honeywell Asia Pacific Inc. Honeywell Europe S.A.
Room 3213-3225
3 Avenue du Bourget
Sun Hung Kai Centre
1140 Brussels
No. 30 Harbour Road
Belgium
Wanchai
Hong Kong
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
OUTDOOR
SENSOR
W964
C
B
A
2
R1
R2
RELAY
RELAY
COIL
COIL
TO MAIN VALVE
TEMINAL ON
PROGRAMMER
R2
2
RELAY
CONTACT
V4062
3
4
1
2
V4055
5
1
2
Honeywell Latin American
Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325
www.honeywell.com/bbc
L1
L2
L2
M7341

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

V4062bV4062d

Table of Contents