Honeywell V4062A Manual page 3

Hi-lo-off fluid power gas valve actuator
Table of Contents

Advertisement

Valve
V5055A,C; V5097A,C 3/4 to 3 in.
V5055A,C 4 in.
V5055B, V5097B 3/4 to 3 in.
V5055B 4 in.
V5055D,E, 3/4, 1, 1-1/4, 1-1/2;
V5097D 3/4 in. to 2 in.
V5055D,E; V5097D,E 2, 2-1/2, 3 in. 5
a
Use a V4062D (with proof-of-closure switch) with a V5055/V5097C or E (with double seal) for valve seal overtravel interlock.
b
Maximum operating pressure differential.
c
Maximum closeoff pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be
subjected when fully closed, and is independent of the valve body rating.
Table 5. Auxiliary Switch and Proof-of-Closure
Switch Ratings (1/2 hp [0.37 kW]
Load
Full Load
9.8A
Locked Rotor
58.8A
a
Maximum total connected power to both switches (if used)
is 1800 VA.
Mounting:
Mounts directly to V5055/V5097 Valve with two setscrews
positioned 90 degrees apart.
Valve and actuator can be mounted in any position
(multipoise).
NOTE: 220 to 240 Vac, 50/60 Hz models must be mounted
vertically.
Mounting Dimensions: See Fig. 1 and Table 7.
Low-Fire Adjustment: 0.17 inch to 0.64 inch (with respect
to V5055/V5097B Valve) valve stem travel.
NOTE: The low-fire position of the V5055/V5097A,C,D and
E Valves differ from the V5055/V5097B. Check the
valve flow curves and match the low-fire position to
the burner design and valve application.
Nominal Opening Time:
Standard Models: 26 sec at 60 Hz; 32 sec at 50 Hz.
Fast-opening Models: 13 sec at 60 Hz; 16 sec at 50 Hz.
Closing Time: 1 sec maximum
Damper Shaft: 3/8 in. sq (9.5 mm) for use with 7616BR
Damper Crank Arm (not included). Models available with or
without damper shaft return spring.
Maximum Damper Shaft Rotation: 52 angular degrees.
Table 4. Pressure Ratings of Valve-Actuators Combinations.
V4062A,D Actuator
b
Differential
psi
mbar
5
340
3
200
5
340
3
200
5
340
340
a
).
120/v
240V
4.9A
29.4A
V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR
a
c
Closeoff
psi
bar
15
1
15
15
1
5
15
1
15
5
1
5
75
5
25
45
3
15
Maximum Force: At 2-11/16 in. (68.3 mm) radius for 7616BR
Damper Crank Arm (ordered separately).
NOTE: Damper shaft drives damper crank arm in one
direction only; optional return spring is available on
damper shaft to turn damper crank arm in opposite
direction. See Table 6.
Table 6. Actuator Torque (With
and Without Return Spring).
V4062 Model
Without return spring 5
With return spring
Ambient Operating Temperature Rating:
-40° to 150°F (-40° to 66°C) for 60 Hz models;
-10° to 158°F (-23° to 70°C) for 50 Hz and 50/60 Hz models.
Approvals:
Underwriters Laboratories Inc. Listed: File No. MH1639,
Guide No. YIOZ.
Factory Mutual: Approved.
International Approval Services (Joint Venture of the
American Gas Association [AGA] and the Canadian Gas
Association [CGA]): Certified 60 Hz models only.
Industrial Risk Insurers Acceptable.
Some V4062 Actuators are approved as Class A valves in
accordance with EN161:
When used with V5055 Valves: Pin: CE-0063AR1359.
When used with VE5000 Series Valves: Pin:
CE-0063AP3075.
Accessories:
133568 Auxiliary Switch Bag Assembly.
133569 Proof-of-Closure Switch Bag Assembly. (Must be
used with a V5055/V5097C or E with double seal).
135796 Wrench (included with the actuator).
7616BR Damper Crank Arm (damper arm and clip).
3
V4062B Actuator
b
Differential
Closeoff
psi
mbar
psi
1000
15
340
15
1000
15
340
15
1700
75
1000
45
-40°F to +20°F
20°F to 150°F
(-40°C to -7°C)
(-7°C to +66°C)
lb
N
lb
22.2
20
5
22.2
10
c
bar
1
1
1
1
5
3
N
89.0
44.5
60-2099—9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

V4062bV4062d

Table of Contents