Specifications; Ordering Information - Honeywell V4062A Manual

Hi-lo-off fluid power gas valve actuator
Table of Contents

Advertisement

V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR

SPECIFICATIONS

IMPORTANT:
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed.
Models:
V4062A HI-LO-OFF Gas Valve Actuator.
V4062B HI-LO-OFF Gas Valve Actuator, high pressure.
V4062D HI-LO-OFF Gas Valve Actuator with proof-of-closure
switch. Use with V5055/V5097C,E (double seal) gas
valves for valve seal overtravel interlock. Do not use
V4062 with V5034 Valve body.
Electrical Ratings:
Standard V4062A,D Actuators (Table 1):
60 Hz, 26 second opening.
50 Hz, 32 second opening.
Table 1. Standard V4062A,D Actuators.
Opening
Voltage/
Frequency
W
120V/60 Hz
59.5
100V/50-60 Hz 53.0/42.7
200V/50-60 Hz 72.01/52.5 160/110
Fast-opening V4062A,D Actuators (Table 2):
60 Hz, 13 second opening.
50 Hz, 16 second opening.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (800) 328-5111
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2099—9
Holding
VA
W
VA
129
19.0
28.0
105/80
20.0/17.2 33/29
18.4/16.2 28/24
Table 2. Fast-opening V4062A,D Actuators.
Voltage/
Frequency
120V/60 Hz
59.5
220V/50 Hz
84.0
220V/50 Hz
82.0
220V-240V; 50-
74.5
a
60 Hz
220V-240V; 50-
61.9
b
60 Hz
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
Fast-opening V4062B Actuators (Table 3):
60 Hz, 13 second opening.
50 Hz, 16 second opening.
Table 3. Fast-opening V4062B Actuators.
Voltage/Frequency
220V-240V; 50-60 Hz
220V-240V; 50-60 Hz
a
230V, 50 Hz power supply.
b
230V, 60 Hz power supply.
Pressure Ratings Of Valve-Actuator Combinations:
See Table 4.
Auxiliary Switch And Proof-Of-Closure Switch Ratings:
See Table 5.
2
Opening
Holding
W
VA
W
129
19.0
196
17.0
180
16.5
143.5
13.7
112
11.2
Opening
W
VA
W
a
76.5
150.6
13.3
64.4
118.2
11
b
VA
28.0
27.0
26.4
24.8
20.5
Holding
VA
28.8
23.2

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the V4062A and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

V4062bV4062d

Table of Contents

Save PDF