V9055A,D Modulating Fluid Power
Gas Valve Actuator

APPLICATION

The V9055 Gas Valve Actuator in combination with a V5055,
a
VE5000
or V5097 Gas Valve provides modulating control of
the gas supply to commercial and industrial burners.
a
VE5000 is a European manufactured and approved valve for
European use only.

FEATURES

• Actuator opens the valve to the low-fire position when
energized. Actuator then modulates to meet firing rate
controller (Series 90) demand.
• Actuator is equipped with an integral shaft that may be
used to drive a combustion air damper in unison with the
gas valve.
• The V5055 or V5097 Gas Valve includes a yellow SHUT
indicator. The actuator includes a red OPEN indicator. The
indicators provide constant visual indication of valve
position.
• Actuator can be used with all VE5000
Valve models; however, the V5055B or V5097B with
characterized guide is recommended for optimum control
and low-fire repeatability.
• Ambient temperature range for 60 Hz models is -40°F to
125°F (-40°C to 53°C). Ambient temperature range for 50
Hz and 50/60 Hz models is -10°F to 125°F
(-23°C to 52°C).
• Auxiliary 1/2 hp rated switch is available for field
installation.
• Integral damper shaft provides a maximum of 20 lb
(9 kg) of force.
• Valve and actuator may be mounted in any position.
• Model is available with NEMA 4 (IP54) weatherproof
enclosure.
• V9055D/V5055C,E and V9055D/V5097C,E combinations
available with proof-of-closure switch and two valve seals
(valve seal overtravel interlock) to meet specific code/
standard/insurer requirements.
• Field addable adapter available for 4-20 dc mA control of
actuator.
• When replacing a V9034 Actuator with a V9055, the V5034
Valve body must also be replaced with a V5055 or V5097
Gas Valve.
NOTICE: Per Industry Standards, the actuator is required a
conduit seal or a cable type that is sealed be installed in a
device that can result in a flammable liquid flow through a
conduit or cable to an electrical ignition source in the event
of a seal leakage or diaphragm failure.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Adjustments ......................................................................
Operation ..........................................................................
Checkout and Service ......................................................
PRODUCT DATA
a
, V5055 or V5097
Contents
1
1
2
2
4
5
6
7
7
60-2311-11

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell V9055A

  • Page 1: Table Of Contents

    V9055A,D Modulating Fluid Power Gas Valve Actuator PRODUCT DATA • The V5055 or V5097 Gas Valve includes a yellow SHUT indicator. The actuator includes a red OPEN indicator. The indicators provide constant visual indication of valve position. • Actuator can be used with all VE5000 , V5055 or V5097 Valve models;...
  • Page 2: Specifications

    TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR Damper Arm Rating (damper drives one direction only): Damper Shaft: Shaft is 3/8 in. (9.5 mm) for use with 7616BR Standard Models: 20 lb. maximum at 2-11/16 in. radius at 20°F Damper Arm. Models available with damper shaft return to 125°F and 5 lb at -40°F to 20°F (9 kg maximum at 68 mm...
  • Page 4: Installation

    V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR Table 4. V9055/V5097 dimensions in inches. (mm) Dim. A Dim. B Dim. C Dim. D Dim. E Dim. F Dim. G Valve Size (in.) Small Body 3/4 11-1/8 282.6 2-3/4 69.9 8-3/16 208.0 5-5/8 142.9...
  • Page 5: Wiring

    V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR Install Accessory Switches (If Needed) LOW FIRE ADJUSTMENT An spdt switch may be installed to operate an auxiliary load of CONNECTIONS up to 1/2 hp. The switch may be adjusted to operate at any...
  • Page 6: Adjustments

    V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR 4. Reconnect power. 5. With manual shutoff gas valve Closed, apply power to PROPORTIONING CONTROLLER the V9055 and check its operations with the 4-20 mA (140 OHM POTENTIOMETER) temperature controller by manually incrementing and decrementing the output;...
  • Page 7: Operation

    V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR OPERATION 1. With manual gas valve closed, energize the V9055 and check for voltage on terminals 1 and 2. Actuator should modulate to the low-fire position. To function as intended, the V9055 must be connected to a properly sized valve.
  • Page 8 V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR 7. If the valve bonnet assembly is in good condition and is not replaced, replace the bonnet seal. Do not reuse the Table 5. Replacement Bonnets for old bonnet seal. See Table 6 below for the seal number.