Direct ignition combination gas control

Advertisement

Quick Links

These direct ignition combination gas controls are used
in gas-fired appliances with capacities up to 300 feet
at 1 inch wc pressure drop [8.5 meters
for natural gas. They include a manual valve, two automatic
operators, a pressure regulator, and a conduit cover. See
Table 1 for temperature ranges and regulator types.
CAPACITY:
Size
(Inlet x Outlet)
1/2 x 1/2
1/2 x 3/4
3/4 x 3/4
a
Capacity based on 1000 Btu/feet
gravity natural gas at 0.25 kPa pressure drop].
TABLE 1—TEMPERATURE RANGES AND
REGULATOR TYPES.
Ambient
Model
Temperature
Number
Range
VR4305H
0° F to 175° F
[-18° C to +79° C]
VR4305M
-40° F to 175° F
[-40° C to +79° C]
VR4305P
-40° F to 175° F
[-40° C to +79° C]
Use conversion factors in Table 2 to convert capacities
for other gases.
TABLE 2—GAS CAPACITY CONVERSION FACTORS.
Specific
Gas
Gravity
Manufactured
Mixed
Propane
Combination Gas Control
Application
3
/hour at 0.25 kPa]
Capacity (at 1 inch
wc pressure drop)
3
240 feet
/hour
3
[6.8 meter
/hour]
3
270 feet
/hour
3
[7.6 meter
/hour]
3
300 feet
/hour
3
[8.5 meter
/hour]
3
, 0.64 specific gravity natural gas at 1 inch wc pressure drop [37.3 MJ/meter
Regulator
Type
Slow-opening
Standard-opening
Step-opening
Multiply Listed
Capacity By
0.60
0.516
0.70
0.765
1.53
1.62
J.D. • Rev. 1-94 • ©Honeywell Inc. 1994 • Form Number 69-0696—1
BODY PATTERN: Straight-through.
INLET X OUTLET SIZES AVAILABLE: 1/2 x 3/4 inch.
ADAPTERS: Adapters available for 1/2 and 3/4 inch straight
and angle connections. Refer to Table 3.
3
/hour
ELECTRICAL RATINGS:
Voltage and Frequency: 120 Vac, 60 Hz.
Thermostat Heat Anticipator Setting: 0.14A.
Current Draw: 0.14A.
Minimum
a
Regulated Capacity
3
30 feet
[0.8 meter
3
30 feet
[0.8 meter
3
30 feet
0.8 meter
TABLE 3—ADAPTER (FLANGE) PART NUMBERS.
Inlet/
Outlet
Pipe Size
1/2 inch NPT
3/4 inch NPT
NOTE: Flange Kits include one flange with attached O-ring
and four mounting screws.
APPROVALS:
American Gas Association design certificate:
L2025007.
Canadian Gas Association design certificate:
L2025007.
Australian Gas Association design certificate:
Applied for.
Delta C.
1
VR4305
Direct Ignition
Regulated Capacity
/hour
340 feet
3
/hour]
[9.6 meter
/hour
370 feet
3
/hour]
[10.5 meter
/hour
415 feet
3
/hour]
[11.8 meter
Without
Flange
Hex
Type
Wrench
Straight
393690-6
Elbow
393690-3
Straight
393690-4
Elbow
393690-5
Maximum
3
/hour
3
/hour]
3
/hour
3
/hour]
3
/hour
3
/hour]
3
, 0.64 specific
Part Number
With
Hex
Wrench
393690-16
393690-13
393690-14
393690-15
69-0696—1

Advertisement

loading

Summary of Contents for Honeywell VR4305

  • Page 1 Canadian Gas Association design certificate: Gravity Capacity By L2025007. Australian Gas Association design certificate: Manufactured 0.60 0.516 Applied for. Mixed 0.70 0.765 Delta C. Propane 1.53 1.62 J.D. • Rev. 1-94 • ©Honeywell Inc. 1994 • Form Number 69-0696—1 69-0696—1...
  • Page 2: Installation

    To convert a gas control from natural to LP gas or from 4. After installation is complete, use these instructions LP to natural gas, contact your Honeywell representative. to check out product operation. Convert standard or slow opening gas controls from one WARNING gas to another with a conversion kit (ordered separately).
  • Page 3 Fig. 1—Install flange to gas control. Fig. 2—Install sediment trap. DROP PIPED 6/32 INCH ROUND HORIZONTAL CONTROL SCREWS (1) SUPPLY CONDUIT RISER COVER CONTROL PIPED 3 INCHES SUPPLY [76] MINIMUM DROP HORIZONTAL 3 INCHES VALVE OUTLET [76] TUBING MINIMUM FLANGE SUPPLY 9/64 INCH HEX SCREWS (4) DO NOT OVERTIGHTEN SCREWS.
  • Page 4 Fig. 4—Top view of gas control. Fig. 6—VR4305 Wiring Connections in S87 Direct Ignition System. CONVENIENCE PRESSURE REGULATOR WIRING TERMINALS (2) ADJUSTMENT (UNDER TERMINALS (2) (HOT) (OPTIONAL) CAP SCREW) LIMIT CONTROLLER OUTLET INLET PRESSURE PRESSURE TAP IGNITION MODULE INLET OUTLET...
  • Page 5: Startup And Checkout

    CHECK AND ADJUST GAS INPUT TO MAIN Startup and Checkout BURNER CAUTION WARNING 1. Do not exceed the input rating stamped on the FIRE OR EXPLOSION HAZARD appliance nameplate, or manufacturer recom- CAN CAUSE PROPERTY DAMAGE, mended burner orifice pressure for the size SEVERE INJURY, OR DEATH orifice(s) used.
  • Page 6 4. If the desired outlet gas pressure or gas flow rate can step function. Repeat after allowing main burner to cool. not be achieved by adjusting the gas control, check the gas Readjust the full rate outlet pressure, if necessary, to im- control inlet pressure by using a manometer at the inlet prove lightoff characteristics.
  • Page 7: Maintenance

    • Do not light any appliances in the house. conditions; i.e., those used in greenhouses or animal barns, • Do not touch electrical switches or use the contact your Honeywell sales representative to request a phone. gas control with corrosion resistant construction.
  • Page 8: Turning Off The Appliance

    STOP! Follow step 2 in the Warning operation. Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario M1P 2V9 QUALITY IS KEY 69-0696—1...