Left column "L"
The table must always start with: L(1)= 0 and r(1)= value (assigned to 0 level)
The table must be ended either with the 32
by a level value "0" e.g. L(j<32)= 0.
The EchoTREK will ignore data after recognising level value "0" with serial number other than "1".
If the above conditions are not met, error codes will be displayed (see chapter: Error Codes).

6.7 Informational Parameters (Read Out Parameters)

P60:
Overall operating hours of the unit (h)
Indication varies according to the elapsed time:
Operating hours
0 to 999.9h
1000 to 9999h
Over 9999h
P61:
Time elapsed after last switch-on (h)
Indication same as in P60.
P64:
Actual temperature of the transducer (°C/°F)
P65:
Maximum temperature of the transducer (°C/°F)
P66:
Minimum temperature of the transducer (°C/°F)
In case of a breaking in the temperature measuring Pt10 element „PtErr" will be displayed (See Chapter 7). The transmitter will perform
temperature correction corresponding to 20ºC.
40
L(1)= 0
L(i)
:
L(j)
data pair i.e. j=32 or if the linearisation table contains less than 32 data-pairs j<32, the table must be closed
nd
Right column "r"
r(1)
r(i)
:
r(j)
Indication form
xxx,x
xxxx
e
X,xx: e meaning x,xx 10
SE/SG-300 series two-wire compact ultrasonic level transmitters