Programming Without Display Module - Echotrek SG-300 Series Installation And Programming Manual

Two-wire compact ultrasonic level transmitters
Table of Contents

Advertisement

5.1 Programming without Display Module

Programming is only possible if the EchoTREK is in Level Measuring
Mode and receives valid echo i.e. "ECHO" LED is lit !
The following can be programmed without display module
Assignment of the 4 mA to a required e.g. min. level / max. distance
Assignment of the 20 mA to a required e.g. max. level / min. distance
Error indication by the current output (Hold, 3.6 mA or 22 mA)
Damping (10, 30 or 60 sec)
Reset to the factory default
Note: Current output can also be assigned in inverted mode:
4 mA = 100% (Full), 20 mA = 0% (Empty)
Procedure of programming: press button in the relevant sequence and check the state of the LED-s. Symbols for the states of the LED-s:
= LED is off,
Minimum level, (0%, empty tank) assignment to 4 mA
Action
1) Check for a valid ECHO
2) Press NEXT
button steadily
3) Press UP
button steadily
4) Release buttons
SE/SG-300 series two-wire compact ultrasonic level transmitters
= LED is blinking,
= LED is on,
Led state following the action
=
Valid ECHO, transmitter programmable
=
EchoTREK in programming mode
=
4 mA assigned to the distance (see picture)
=
Programming completed
= LEDs are blinking alternatively
Use level in tank or a fix target e.g. the wall
= Dont care