Condensate Water Pipe; Insulation Material; Communication Cable And Control Cable; Power Cable - Gree GMV-160WL/A-T Service Manual

Dc inverter multi vrf system ii
Hide thumbs Also See for GMV-160WL/A-T:
Table of Contents

Advertisement

OD (mm/inch)
Φ6.35(1/4)
Φ9.52(3/8)
Φ12.70(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
f. After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed tightly
by using pipe caps, plugs or adhesive tapes.

2.2 Condensate water pipe

a. Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R pipe,
PP-C pipe, and HDG steel pipe;
b. All relevant certificates and quality test reports are provided.
c. Requirements for specifications and wall thickness
Water supplying UPVC pipe: Φ32mm×2mm,Φ40mm×2mm,Φ50mm×2.5mm;
HDG steel pipe: Φ25mm×3.25mm,Φ32mm×3.25mm,Φ40mm×3.5mm,Φ50mm×3.5mm.

2.3 Insulation material

a. Rubber foam insulation material;
b. Flame retardancy level: B1 or higher;
c. Refractoriness: at least 120℃;
d. The insulation thickness of condensate water pipe: at least 10 mm;
e. When the diameter of copper pipe is equal to or greater than Φ15.9 mm, the thickness of insulation
material should be at least 20 mm; when the diameter of copper pipe is less than 15.9 mm, the
thickness of insulation material should be at least 15 mm.

2.4 Communication cable and control cable

Note: For air conditioning units installed in places with strong electromagnetic interference, shielded
wire must be used as the communication cables of the IDU and wired controller, and shielded twisted
pairs must be used as the communication cables between IDUs and between the IDU and ODU.
Communication cable selection for ODU and IDUs
Wire Type
Common sheath
twisted pair copper
core (RVV)
Communication cable selection for IDU and wired controller
Wire Type
Common sheath
twisted pair copper
core (RVV)

2.5 Power cable

Only copper conductors can be used as power cables. The copper conductors must meet relevant
national standard and satisfy the carrying capacity of unit.

2.6 Hanger rod and support

a. Hanger rod: M8 or M10;
DC Inverter Multi VRF System II Service Manual
R410A Refrigerant System
Communication Cables
Between IDU and
Indoor (Outdoor) Unit
L(m)
L≤1000
Total Length of
Communication Cables
of the IDU and Wired
Controller L(m)
L≤250
Wall Thickness (mm)
≥0.8
≥0.8
≥0.8
≥1.0
≥1.0
Number of Wire Pieces
2
x Wire Diameter (mm
)
≥2×0.75
Number of Wire Pieces
2
x Wire Diameter (mm
)
≥2×0.75
57
Wire Standard
If the wire diameter is
enlarged to 2×1mm2,
GB/T 5023.3-2008
communication length
Wire Standard
GB/T 5023.3-2008
communication length
cannot exceed 250 m.
Model
0
0
0
0
0
Remark
the overall
can reach 1500 m.
Remark
The overall