The timing diagram of parameter access shows as follows:
5.3 Identification and Maintenance Functions (I&M)
Identification and maintenance (I&M) is to provide you with supports in adjustment,
test, parameterization and repair.
CMC-PN01 supports I&M0 functions and access by read requests that record data
objects.
The table below shows the data structure of I&M0 functions:
Content
Header
Vendor ID
Order ID
Serial number
Hardware revision
Software revision
Revision counter
Profile ID
Profile specific type
I&M version
Supported I&M functions

5.4 Disconnection Treatment

When PROFINET is disconnected, CMC-PN01 performs the following settings to
ensure safety.
1.
Set 2505H = 81Ecto indicates CMC-PN01 occurs a disconnection failure
2.
Set 6000H = 0
3.
Set 2000H = 1
When PROFINET connection restores, it resumes performing commands from the
host controller.
CMC-PN01 Operation Manual
VFD-C2000 PROFINET Communication Card CMC-PN01
Field for transferring additional data
Field for transferring additional data
24 bytes for request; 20 bytes for response.
Used only with request and read response.
Size
10 bytes
-
2 bytes
PROFINET Vendor ID of Delta, which is 0x03BF.
20 bytes
Order number
16 bytes
Serial number
2 bytes
Hardware revision
4 bytes
Revision of the software
2 bytes
Number of revision
2 bytes
0x00
2 bytes
No profile specific type (0x0000)
2 bytes
Version 1.1 (0x0101)
2 bytes
I&M0 is supported (0x0001).
-
-
Description
UI16
UI16